Page 77

background image

SECTION 18: S

PECIFICATIONS

71 of 73

SECTION 18: SPECIFICATIONS

18.1 Material Specifications

18.1.1 Combustion and Tubes

100 mm dia. 16 gauge heat treated aluminised
mild steel.

18.1.2 Reflectors

NS3 H14 aluminium or 1.4016 2R stainless
steel (option).

18.2 Heater Specifications

18.2.1 Sequence Controller

Fully automatic, single try, direct spark,
100% shut off ignition flame rectification module.

18.2.2 Electrical

Rating: 230 V, 50 Hz, 1 Ø, 1 A

Connection: minimum IP55 junction box

18.2.3 Gas Supply

Connection: Rc1/2 (1/2" BSP int)

Natural G20:

Minimum - Inlet 15 mbar (6 in wg)

Maximum - Inlet 50 mbar (20 in wg)

Natural G25:

Minimum - Inlet 17.5 mbar (7 in wg)

Maximum - Inlet 50 mbar (20 in wg)

LP Gas (Propane or Butane):

Minimum - Inlet 32.5 mbar (13 in wg)

Maximum - Inlet 50 mbar (20 in wg)

18.3 Venting Specifications

18.3.1 Fans

HE15, 20, 25, 30, 35 ....... Model: Torin DSF 133-42

HE40, 45, 50 ................... Model: AO Smith JF1G

HE30DL, 40DL................. Model: Torin DSA 524-202

HE50DL, 60DL,70DL ....... Model: Magnetek JF1G

18.3.2 IP54 Protected Fans

HE15, 20, 25, 30, 35 ........ Model: Torin DSA 508-128

(P/N 90710051)

HE40, 45, 50 .................... Model: Torin DSF 146-052

(P/N 90710053)

HE30DL, 40DL ................ Model: Torin DSA 524-202

(P/N 90710052)

HE50DL - 70DL ............... Model: Torin DSF 146-052

(P/N 90710053)

Multiburner ...................... Model: Airflow 83 BTLW IP55

...................... Model: Airflow 90 BTLW IP55

Consult the manufacturer for availability of alternate fans.

18.3.3 Flue

The flue must be 100 mm, or greater in diameter, and
must conform to National Codes. The flue must be self
supporting. Inlet must be 100 mm diameter.

Multiburner - Flue will be 150 mm diameter. Flue material
must conform to National Codes. The flue must be self
supporting.

18.4 Suspension Specifications

Hang heater with materials with a minimum working load
of 33 kg.

18.5 Controls Specifications

Time switches, thermostats, etc. can be wired into the
electrical supply. External controls supplied as an
optional extra.