14.5 Troubleshooting for Solenoid Valves Circuit

14.6 Troubleshooting for Main Fan Circuit (1 Ø)

Fault lies elsewhere.

Investigate and correct.

Valve faulty.

Replace with correct type.

Yes

No

Is there an electrical supply

to the valve terminals?

Valve faulty.

Replace with correct type.

Fault lies elsewhere.

Investigate and correct.

Valve Operating

TROUBLESHOOT ENDS.

If problems persist, contact

ROBERTS GORDON

®

at

Tel: +44 (0)121 506 7709

www.rg-inc.com

No

Yes

Does valve open at the

correct time?

No

Yes

Yes

START

No

No

Is there pressure on the

outlet of the valve when the

valve should be closed?

Is there an electrical supply

to the valve terminals?

Motor running.

TROUBLESHOOT ENDS.

If problems persist, contact

ROBERTS GORDON

®

at

Tel: +44 (0)121 506 7709

www.rg-inc.com

No

Thermal overload in motor

is faulty.

Replace complete fan unit.

Yes

No

Motor stops after running

some time.

Fan thermostat faulty.

Replace and reset.

Check calibration of the

fan thermostat.

The dial should indicate

the approximate

temperature of the

sampled air.

Fault lies elsewhere.

Yes

No

Re check supply to

terminals L1 to N.

Yes

No

Check the setting of the

fan thermostat as in

Figure 13.

Yes

No

Check and test wiring to

motor. Does the motor run

now?

Motor faulty.

Replace complete fan unit.

Yes

Yes

START

No

No

Main fan will not operate

following warm up

period of heat exchanger.

Check for 230 V

at terminals 1 to N.

Press in white button

of fan/limit thermostat

and retest.

For your safety and optimum heater performance, use only ROBERTS GORDON

®

replacement parts.

Conduct Commissioning procedure as shown on Page 33, Section 10.