SECTION 4: S

PECIFICATIONS

9

4.6 Technical Data - Ecoflam Modulating Burners (all models - burner reference "H")

NOTE: The air setting is a guide only. The final setting is subject to combustion testing.

When setting the minimum firing rate, a check must be made following the setting of the burner combustion. The
check is made by running the heater on low fire for a minimum of 15 minutes at the full transport air rate and at typical
ambient conditions. During the test, check that the flue gas temperature does not fall below 125° C. Should the flue
gas temperature fall below 100° C, then the low fire gas setting must be increased to a value that will achieve 125° C
flue gas temperature; otherwise condensation may form in the heat exchanger and flue, causing rapid corrosion and
short operational life.

NOTE: For adjustment of head setting, see Ecoflam Instructions.

Model

015

020

030

040

050

060

070

080

0100

Maximum Gross Heat Input

(kW)

(Btu/h) x (1000)

55.5

189.4

73.3

250.1

93.2

318.0

129.9
443.2

162.0
552.7

208.0
709.7

242.0
825.7

275.2
939.0

348.5

1189.1

Maximum Net Heat Input

(kW)

(Btu/h) x (1000)

50.0

170.6

66.0

225.2

84.0

286.6

117.0
399.2

146.0
498.2

187.4
639.4

218.0
743.8

248.0
846.2

314.0

1071.4

Minimum Gross Heat Input

(kW)

(Btu/h) x (1000)

38.9

132.7

51.3

175.0

65.2

222.5

90.9

310.2

113.4
386.9

145.6
496.8

169.4
578.0

192.6
657.2

244.0
832.5

Minimum Net Heat Input

(kW)

(Btu/h) x (1000)

35.0

119.4

46.2

157.6

58.8

200.6

81.9

279.5

102.2
348.7

131.2
447.7

152.6
520.7

173.6
592.3

219.8
750.0

Maximum Heat Output

(kW)

(Btu/h) x (1000)

47.4

161.7

61.2

208.8

78.4

267.5

110.2
376.0

134.5
458.9

177.7
606.3

205.3
700.5

230.4
694.0

293.4

1001.1

Minimum Heat Output

(kW)

(Btu/h) x (1000)

33

113

43

147

55

188

77

263

94

321

124
423

144
491

161
549

205
699

Pressure Switch Setting

(mbar)

1.5

1.0

1.5

2.0

2.5

Flue Static Pressure

(mbar)

-0.05

-0.05

-0.09

-0.30

-0.05

-0.25

-0.17

0.10

0.45

Gas Connection

(in)

3/4"

1 1/4"

Natural Gas (G20) Data - Inlet Pressure 20 mbar (7.8 in WG) Min 17 mbar (6.8 in WG) Max 25 mbar (10 in WG)

Main Burner Gas Pressure

(mbar)

4.9

2.4

3.3

4.1

6.7

5.2

6.7

8.0

8.6

Min. Burner Gas Pressure

(mbar)

3.2

2.8

2.4

2.3

3.7

2.5

3.4

4.3

5.4

Start Gas Pressure

(mbar)

NA

NA

NA

1.1

1.8

0.6

0.7

0.9

1.0

Maximum Gas Rate

(m

3

/h)

(ft

3

/h)

5.3

187

7.0

247

8.9

314

12.4

438

15.4

544

19.8

699

23.1

816

26.2

925

33.2

1172

Minimum Gas Rate

(m

3

/h)

(ft

3

/h)

3.8

134

5.0

177

6.3

222

8.8

311

11.0

388

14.2

501

16.5

583

18.7

660

23.7

837

Start Gas Orifice

(mm dia)

NA

NA

NA

7.0

Burner Type

AZUR 60

BLU 120

BLU 120

BLU 170

BLU 250R

BLU 250

BLU 250

BLU 250

BLU 350

Burner Head

S

S

S

S

S

S

S

S

S

Burner Head Setting

(mm)

0.0

8.0

10.0

15.0

14

T.O.

Low Flame Air Orange Cam

**

20°

13°

22°

18°

22°

25°

High Flame Air Red Cam

**

33°

40°

80°

30°

32°

30°

35°

55°

60°

Gas Valve Setting

0-1, 5

0-1

0-1, 4

Valve Type Main Gas

MBDLE 407

MBDLE 412

Valve Type Start Gas

NA

S.I.T. 0 832 051

LPG Gas Propane (G31) Data - Inlet Pressure 37 mbar (14.6 in WG) Min 25 mbar (10 in WG) Max 45 mbar (18 in WG)

Main Burner Gas Pressure

(mbar)

4.3

5.7

4.7

3.1

5.9

5.3

7.2

9.0

6.4

Min. Burner Gas Pressure

(mbar)

2.3

2.9

1.4

1.6

2.0

2.3

2.5

3.2

2.0

Start Gas Pressure

(mbar)

NA

NA

NA

1.1

1.7

0.6

0.7

0.7

1.5

Maximum Gas Rate

(m

3

/h)

(kg/h)

2.09
3.87

2.76
5.11

3.51
6.49

4.89
9.05

6.10

11.29

7.83

14.49

9.11

16.86

10.36
19.18

13.12
24.29

Minimum Gas Rate

(m

3

/h)

(kg/h)

1.46
2.71

1.93
3.58

2.46
4.55

3.42
6.34

4.27
7.90

5.48

10.15

6.38

11.80

7.25

13.42

9.18

17.00

Start Gas Orifice

(mm dia)

NA

NA

NA

7.0

Main Gas Orifice

(mm dia)

8.5

10.0

14.5

NA

Burner Type

AZUR 60

BLU 120

BLU 120

BLU 170

BLU 250R

BLU 250

BLU 250

BLU 250

BLU 350

Burner Head

S

S

S

S

S

S

S

S

S

Burner Head Setting

(mm)

0.0

8.0

10.0

15.0

14

T.O.

Low Flame Air Orange Cam

**

20°

13°

22°

18°

22°

25°

High Flame Air Red Cam

**

33°

40°

80°

30°

32°

30°

35°

55°

60°

Gas Valve Setting

0-1, 4

0, 3-0, 9

0-1, 1

0-1, 4

0-1, 5

0-0, 85

Valve Type Main Gas

MBDLE 407

MBDLE 412

Valve Type Start Gas

NA

S.I.T. 0 832 051