Warning – Roberts Gorden Combat Cabinet Heaters POP-ECA/PGP-ECA 015 to 0100 User Manual
Page 52

COMBAT
®
C
ABINET
H
EATERS
I
NSTALLATION
, C
OMMISSIONING
, O
PERATION
AND
S
ERVICE
M
ANUAL
46
14.2 Troubleshooting for Oil Burners (see manufacture’s instructions)
Heater Operating
TROUBLESHOOT ENDS.
If problems persist, contact
ROBERTS GORDON
®
at
Tel: +44 (0)121 506 7709
www.rg-inc.com
No
Check oil solenoid valve.
No
Check ignition electrodes are
set as in the manufacturer's
instructions, the fuel supply
and nozzle.
Yes
No
Does the burner control
box 'lockout' after 15
seconds?
Control box faulty.
Repair or replace.
Use Section 14.4 to
trace fault.
Yes
Yes
No
No
Does the burner control
box 'lockout' before 15
seconds?
Repair or replace.
Check control box.
No
Check supply to burner
motor.
Yes
No
Check if the control fuse in
the heater has blown.
Disconnect photo cell
and try again.
Yes
No
Did the burner fire?
Yes
No
START
Assuming fuel & electrical
supplies are ON
Yes
No
Does the burner fire?
Use Section 14.4 to
trace fault.
WARNING
Electrical Shock Hazard
Do not touch ignition components.
Voltage from ignition components is high.
Failure to follow these instructions can
result in death or electrical shock.
For your safety and optimum heater performance,
use only ROBERTS GORDON
®
replacement parts.
Conduct Commissioning procedure as shown
on Page 33, Section 10.