14.2 Troubleshooting for Oil Burners (see manufacture’s instructions)

Heater Operating

TROUBLESHOOT ENDS.

If problems persist, contact

ROBERTS GORDON

®

at

Tel: +44 (0)121 506 7709

www.rg-inc.com

No

Check oil solenoid valve.

No

Check ignition electrodes are

set as in the manufacturer's

instructions, the fuel supply

and nozzle.

Yes

No

Does the burner control

box 'lockout' after 15

seconds?

Control box faulty.

Repair or replace.

Use Section 14.4 to

trace fault.

Yes

Yes

No

No

Does the burner control

box 'lockout' before 15

seconds?

Repair or replace.

Check control box.

No

Check supply to burner

motor.

Yes

No

Check if the control fuse in

the heater has blown.

Disconnect photo cell

and try again.

Yes

No

Did the burner fire?

Yes

No

START

Assuming fuel & electrical

supplies are ON

Yes

No

Does the burner fire?

Use Section 14.4 to

trace fault.

WARNING

Electrical Shock Hazard

Do not touch ignition components.

Voltage from ignition components is high.

Failure to follow these instructions can

result in death or electrical shock.

For your safety and optimum heater performance,
use only ROBERTS GORDON

®

replacement parts.

Conduct Commissioning procedure as shown
on Page 33, Section 10
.