Warning – Roberts Gorden Combat Cabinet Heaters POP-ECA/PGP-ECA 015 to 0100 User Manual
Page 51

SECTION 14: T
ROUBLESHOOTING
45
SECTION 14: TROUBLESHOOTING
14.1 General
WARNING
Explosion Hazard
Installation must be done by a registered installer/
contractor qualified in the installation and service of
gas-fired heating equipment or your gas supplier.
Failure to follow these instructions can result in death,
injury or property damage.
Replace fan/limit
thermostat.
See Figure 13 to check
thermostat settings.
No
Use 14.6 or 14.7 to test fan.
Yes
No
Check external controls are
ON and the fuse in the
burner is sound.
Test burner as in
14.2 (oil-fired),
14.3 (gas-fired).
Repair or Replace.
Yes
No
Check if the control fuse in
the heater has blown.
Yes
No
Is the 'lockout' button on the
burner alight?
Test burner as in
14.2 (oil-fired),
14.3 (gas-fired).
Heater Operating
TROUBLESHOOT ENDS.
Press in the white button on
fan/limit thermostat.
Does the burner stop after
running for several minutes
with controls still ON ?
If problems persist, contact
ROBERTS GORDON
®
at
Tel: +44 (0)121 506 7709
www.rg-inc.com
Did burner 'lockout' ?
Check main fan for blockage
or belt tension and correct
rotation.
Check operation and setting
of fan/limit thermostat. Repair
or replace as necessary.
START
Assuming fuel & electrical
supplies are ON
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Does the burner fire?
Does the main fan run?
For your safety and optimum heater performance, use only ROBERTS GORDON
®
replacement parts.
Conduct Commissioning procedure as shown on Page 33, Section 10.