Powerware 9315 Parallel Redundant System I & O

164202013, Rev. D 041599

Table A--3. Tie Cabinet Power Inputs and Termination Requirements

UPS

Model

UPS

Output

NP

Voltage

Minimum

Conductor

Size

Breakers

MOB 1

and 2

(Amps)

Terminal

Point in

Tie

Cabinet

Function

Size of

Pressure

Termination

(CU wire)

Tightening

Torque

(lb-in)

Internal

Hex Size

(In.)

40

400

4 AWG

80

E9, E10,

E11

Phase A,

B, C

#14-3/0

#14--#10, (35)

#8--#3, (100)

#2--#3/0, (150)

7/32

50

600

6 AWG

60

E9, E10,

E11

Phase A,

B, C

#14-3/0

#14--#10, (35)

#8--#3, (100)

#2--#3/0, (150)

7/32

50

480

4 AWG

80

E9, E10,

E11

Phase A,

B, C

#14-3/0

#14--#10, (35)

#8--#3, (100)

#2--#3/0, (150)

7/32

50

208

2/0 AWG

175

E9, E10,

E11

Phase A,

B, C

#8-350 kcmil #8--#4, (150)

#3--#1, (200)

#1/0-350

kcmil, (250)

5/16

65

400

1 AWG

125

E9, E10,

E11

Phase A,

B, C

#8-350 kcmil #8--#4, (150)

#3--#1, (200)

#1/0-350

kcmil, (250)

5/16

80

600

3 AWG

100

E9, E10,

E11

Phase A,

B, C

#8-350 kcmil #8--#4, (150)

#3--#1, (200)

#1/0-350

kcmil, (250)

5/16

80

480

1 AWG

125

E9, E10,

E11

Phase A,

B, C

#8-350 kcmil #8--#4, (150)

#3--#1, (200)

#1/0-350

kcmil, (250)

5/16

80

400

1/0 AWG

150

E9, E10,

E11

Phase A,

B, C

#8-350 kcmil #8--#4, (150)

#3--#1, (200)

#1/0-350

kcmil, (250)

5/16

80

208

350 kcmil 300

E9, E10,

E11

Phase A,

B, C

(2) #2/0-400

kcmil or

(1) #6-600

kcmil

#2--600 kcmil,

(375)

#8-#3, (275)

3/8

125

400

4/0 AWG

225

E9, E10,

E11

Phase A,

B, C

#8-350 kcmil #8--#4, (150)

#3--#1, (200)

#1/0-350

kcmil, (250)

5/16

130

400

250 kcmil 250

E9, E10,

E11

Phase A,

B, C

#8-350 kcmil #8--#4, (150)

#3--#1, (200)

#1/0-350

kcmil, (250)

5/16

continued