beautypg.com

Power wiring details – Powerware 9315 User Manual

Page 28

background image

22

Powerware 9315 Parallel Redundant System I & O

164202013, Rev. D 041599

Power Wiring Details

Each UPS module must be wired to its corresponding module output breaker in the

cabinet with power cables sufficient for carrying the load. Recommended wiring

size is listed in Tables A---3 and A---4 of Appendix A of this manual. Each of the

three phases plus the neutral must be wired. Nonlinear loads can create neutral

currents that are greater than 100%. The neutral bus (terminal strip E12) contains

sufficient cable landing to wire double-size neutrals if needed.

NOTE: Material and labor for external wiring are to be provided by designated

personnel.