Troubleshooting – Lochinvar Power-fin 1701 User Manual

Page 42

background image

3

Troubleshooting

42

Service Manual

FAULT

DESCRIPTION

CORRECTIVE ACTION

Service Blk

While the unit is in Service Mode, the outlet
temperature has exceeded 185°F (85°C).

• Establish a heating load to remove heat from the

system.

• Verify that the system is full of water and that all air

has been properly purged from the system.

• Verify that the appliance is piped properly into the

system. Refer to Section 4 - Water
Connections
of the Power-fin Installation and
Operation Manual for the proper piping methods.

• Check 120 VAC to the pump motor on a call for

heat. If voltage is not present, check the wiring
leading to the main control board. Replace the main
control board if necessary.

• If 120 VAC is present on a call for heat and the

pump is not operating, replace the pump.

Low Voltage

120 VAC input to the main control board has
dropped below 80 VAC.

• Check 120 VAC supply to the transformer.

• Check wiring connections at the low voltage terminal

strip.

• Check the wire size/length to remote devices.

• Replace the main control board.

Watch Dog Error

The main control board has detected an
internal fault.

• Replace the main control board.

Write EEProm

The main control board has detected an
internal fault.

• Replace the main control board.

Program EEProm

The main control board has detected an
internal fault.

• Replace the main control board.

CRC Parameters

The main control board has detected an
internal fault.

• Replace the main control board.

No Error Stored

The main control board has detected an
internal fault.

• Replace the main control board.