beautypg.com

Troubleshooting, Checking temperature sensors – Lochinvar Power-fin 1701 User Manual

Page 33

background image

3

Troubleshooting

(continued)

Service Manual

33

Temperature

Resistance

Temperature

Resistance

50

18,780

158

1,990

68

12,263

176

1,458

86

8,194

194

1,084

104

5,592

212

817

122

3,893

140

2,760

Temperature

Resistance

Temperature

Resistance

68

125,500

158

16,870

77

100,000

176

12,000

86

80,220

194

8,674

104

52,590

212

6,369

122

35,270

230

4,744

140

24,160

248

3,581

Temperature

Resistance

Temperature

Resistance

-50

490,813

20

46,218

-40

336,606

30

34,558

-30

234,196

40

26,099

-20

165,180

50

19,900

-10

118,018

60

15,311

0

85,362

70

11,883

10

62,465

80

9,299

Checking temperature sensors

The appliance temperature sensors (inlet water, outlet water, system water, tank water, flue, and outdoor air) are all resistance
type devices. The following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read
the resistance of the sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding
table, replace the sensor.

Table 3B Inlet/Outlet/System/Tank Sensor Resistance vs. Temperature

Table 3C Flue Temperature Sensor Resistance vs. Temperature

Table 3D Outdoor Air Sensor Resistance vs. Temperature