Troubleshooting, Checking temperature sensors – Lochinvar Power-fin 1701 User Manual
Page 33
3
Troubleshooting
(continued)
Service Manual
33
Temperature
Resistance
Temperature
Resistance
50
18,780
158
1,990
68
12,263
176
1,458
86
8,194
194
1,084
104
5,592
212
817
122
3,893
140
2,760
Temperature
Resistance
Temperature
Resistance
68
125,500
158
16,870
77
100,000
176
12,000
86
80,220
194
8,674
104
52,590
212
6,369
122
35,270
230
4,744
140
24,160
248
3,581
Temperature
Resistance
Temperature
Resistance
-50
490,813
20
46,218
-40
336,606
30
34,558
-30
234,196
40
26,099
-20
165,180
50
19,900
-10
118,018
60
15,311
0
85,362
70
11,883
10
62,465
80
9,299
Checking temperature sensors
The appliance temperature sensors (inlet water, outlet water, system water, tank water, flue, and outdoor air) are all resistance
type devices. The following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read
the resistance of the sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding
table, replace the sensor.
Table 3B Inlet/Outlet/System/Tank Sensor Resistance vs. Temperature
Table 3C Flue Temperature Sensor Resistance vs. Temperature
Table 3D Outdoor Air Sensor Resistance vs. Temperature