Troubleshooting – Lochinvar Power-fin 1701 User Manual

Page 37

background image

3

Troubleshooting

(continued)

Service Manual

37

FAULT

DESCRIPTION

CORRECTIVE ACTION

No Flame

Running

(Will require a manual

reset once the condition

has been corrected. Press

the RESET button on the
SMART SYSTEM display

to reset.)

The unit was running and lost the flame signal. • Inspect igniter and associated wiring for damage and

connection. Reference page 25 of this manual for
removal and cleaning procedure. Replace if
necessary.

• Check for proper electrical grounding of unit.

• Check incoming supply gas pressure. Refer to

Section 3 - Gas Connections of the Power-fin
Installation and Operation Manual for detailed
information concerning the gas supply.

• Verify that the tube from the gas valve to the air inlet

is connected and is not damaged.

• Verify that the vent/air intake pipes are installed

correctly and there are no obstructions.

• Refer to the Checking Manifold Gas Pressure and

Combustion Analysis Procedure on pages 27 and 28
of this manual for the proper settings.

• Inspect the burner. Reference page 26 of this

manual for removal and cleaning procedures.
Replace if necessary.

• Replace the main control board.

Auto Reset

High Limit

The outlet water temperature has exceeded the
fixed setting of the automatic reset high limit.

• Verify that the system is full of water and that all air

has been properly purged from the system.

• Verify that the appliance is piped properly into the

heating system. Refer to Section 4 - Water
Connections
of the Power-fin Installation and
Operation Manual for the proper piping methods
for the Power-fin.

• Check 120 VAC to boiler pump motor on a call for

heat. If voltage is not present, check wiring back
to the main control board. Replace the main
control board if necessary.

• If 120 VAC is present on a call for heat and the

pump is not operating, replace the pump.

• If the system pump is a variable speed pump,

ensure that the system flow is not less than the
boiler flow.

• Check temperature setting of the main control

board.

• Check resistance of water sensors and compare to

Table 3B on page 33 of this manual. Replace
sensor if necessary.

• Replace high limit.