beautypg.com

Maintenance, Inspect and clean the heat exchanger, Review with owner – Lochinvar Power-fin 1701 User Manual

Page 30: Oiled bearing circulators

background image

2

Maintenance

30

Service Manual

Inspect and clean the heat exchanger

Figure 2-7_Location of the Heat Exchanger Inside
Jacket

1.

Turn off all power to the appliance.

2.

Turn off main gas to appliance.

3.

Remove the front outer jacket panel.

4.

Remove the inner jacket panel (see FIG. 2-7).

5.

Check the heat exchanger surface for soot. If soot is
present, the heat exchanger must be cleaned and the
problem corrected.

6.

Remove the burner as described in the Inspect and
Clean Burner
section of this manual.

7.

Check the “V” baffles on the heat exchanger. Remove
and clean if necessary.

8.

Remove soot from the heat exchanger with a stiff bristle
brush. Use a vacuum to remove loose soot from
surfaces and inner chamber.

9.

The heat exchanger can be removed by disconnecting
all water piping to the heat exchanger, removing the
screws holding the heat exchanger to the top of the
inner jacket and sliding the heat exchanger towards the
front of the appliance. Once the heat exchanger is
removed, a garden hose can be used to wash the tubes
to ensure that all soot is removed from the heat
exchanger surfaces. Note: Do not wet the insulation
blankets on the inside of the outer jacket panels.

10. Ensure that any soot present on the burner is removed.

See Inspect and Clean Burner section.

11. Carefully reinstall the heat exchanger and “V” baffles if

removed from the appliance.

12. Reinstall the inner jacket panel, burner, manifolds,

wires, and hoses. Use new gasket material to ensure a
proper air seal.

13. Reassemble all gas and water piping. Test for gas leaks.

Upon completion of any testing on the gas
system, leak test all gas connections with a
soap and water solution while main burners
are operating. Do not spray soap and water
solution on the SMART SYSTEM control
module housing. The use of an excessive
amount of soap and water solution can
damage the control. Immediately repair any
leak found in the gas train or related
components. Do not operate an appliance
with a leak in the gas train, valves, or related
piping.

NOTICE

14. Reassemble outer jacket panels.

15. Cycle unit and check for proper operation.

Review with owner

1. Review the Power-fin User’s Information Manual with the

owner.

2. Emphasize the need to perform the maintenance schedule

specified in the Power-fin User’s Information Manual (and
in this manual as well).

3. Remind the owner of the need to call a licensed contractor

should the appliance or system exhibit any unusual
behavior.

4. Remind the owner to follow the proper shutdown procedure

and to schedule an annual start-up at the beginning of the
next heating season.

Oiled bearing circulators

Inspect the pump every six (6) months and oil as necessary. Use
SAE 30 non-detergent oil or lubricant specified by the pump
manufacturer.

This manual is related to the following products: