Maintenance

22

Service Manual

Maintenance and annual startup

Service technician

(see the following pages for instructions)

General:

• Address reported problems

• Inspect interior; clean and vacuum if

necessary;

• Inspect condensate system and flush with

fresh water

• Check for leaks (water, gas, flue,

condensate)

• Examine venting system

• Check system water pressure/system

piping/expansion tank

• Check control settings

• Check igniter

• Check wiring and connections

• Check flue gas passageways

• Flame inspection (stable, uniform)

• Inspect and clean the burner

• Check manifold gas pressure

• Clean the heat exchanger if flue

temperature is more than 54°F (30°C)
above return water temperature.

• Perform start-up checkout and

performance verification per Section 7
in the Power-fin Installation and Operation
Manual.

If combustion or performance
indicate need:

• Clean heat exchanger

• Remove and clean burner using

compressed air only

• Clean the blower wheel

ANNUAL

ST

ART

-UP

Owner maintenance

(see the Power-fin User’s Information Manual for

instructions)

Daily

• Check appliance area

• Check pressure/temperature

gauge

Monthly

• Check vent piping

• Check air piping

• Check relief valve

• Check condensate drain system

Periodically

• Test low water cutoff (if used)

• Reset button (low water cutoff)

Every

6 months

• Check appliance piping (gas and

water) for leaks

• Operate relief valve

End

of season

months

• Shut appliance down (unless

boiler used for domestic hot
water)

Table 2A_Service and Maintenance Schedules