Determine boiler location

(continued)

ALCOVE INSTALLATION

OPEN
FRONT

1" MINIMUM CLEARANCE

AROUND HOT WATER

PIPES AND VENT PIPE

0”

RIGHT

18”

FRONT

14”

REAR

12”

LEFT

13”

TOP

RECOMMENDED SERVICE CLEARANCES:

FRONT -

24”

TOP

-

24”

LEFT SIDE - 24”
REAR

- 24”

Figure 1-2 Alcove Installation - Minimum Required Clearances

CLOSET INSTALLATION

CLOSED DOOR

VENTILATING*
AIR OPENING

VENTILATING*
AIR OPENING

*

AREA OF EACH OPENING:
1 SQ. INCH PER 1000 BTU PER HOUR INPUT
WITH A MINIMUM OF 100 SQ. INCHES.

6"

6"

1" MINIMUM CLEARANCE

AROUND HOT WATER

PIPES AND VENT PIPE

0"

RIGHT

6"

FRONT

14"

REAR

12"

LEFT

13”

TOP

RECOMMENDED SERVICE CLEARANCES:

FRONT -

24”

TOP

-

24”

LEFT SIDE - 24”
REAR

- 24”

Figure 1-1 Closet Installation - Minimum Required Clearances

ƽ WARNING

For closet installations, CPVC or
stainless steel vent material MUST
BE used in a closet structure due to
elevated temperatures. Failure to
follow this warning could result in
fire, personal injury, or death.

ƽ WARNING

For alcove installations, CPVC or
stainless steel vent material
MUST BE used in an alcove
structure due to elevated
temperatures. Failure to follow
this warning could result in fire,
personal injury, or death.