Figure 3-11 Near Boiler Stainless Steel Venting Model 286

Stainless steel air intake/vent connections

1.

Combustion Air Intake Connector (FIG. 3-11) - Used to
provide combustion air directly to the unit from
outdoors. A fitting is provided on the unit for final
connection. Combustion air piping must be supported
per guidelines listed in the National Mechanical Code,
Section 305, Table 305.4 or as local codes dictate.

2.

Vent Connector (FIG. 3-11) - Used to provide a
passageway for conveying combustion gases to the
outside. A transition fitting is provided on the unit for
final connection. Vent piping must be supported per the
National Building Code, Section 305, Table 305.4 or as
local codes dictate.

The Knight boiler uses model specific combustion air intake
and vent piping sizes as detailed in Table 3C below.

Model

Air Intake

Vent

81 - 211

3 inches

3 inches

286

4 inches

4 inches

Table 3C Air Intake/Vent Piping Sizes

Increasing or decreasing combustion air
or vent piping is not authorized.

NOTICE

Minimum / Maximum allowable
combustion air and vent piping lengths
are as follows:

Combustion Air = 12 equivalent feet minimum / 100
equivalent feet maximum

Vent = 12 equivalent feet minimum / 100 equivalent feet
maximum

When determining equivalent combustion air and vent length,
add 5 feet for each 90° elbow and 3 feet for each 45° elbow.

EXAMPLE: 20 feet of PVC pipe + (4) 90° elbows + (2) 45°
elbows + (1) concentric vent kit (CVK3003) = 49 equivalent
feet of piping.

The appliance output rating will reduce by
up to 1.5% for each 25 feet of vent length.

NOTICE

3

General venting

(continued)

Table 3B Approved Stainless Steel Terminations and Adapters

Model

ProTech

Heat Fab

Z Flex

FasNSeal

Saf-T Vent

Z-Vent

Boiler

Adapter

Flue

Termination

Intake

Air

Termination

Boiler

Adapter

Intermediate

Adapter

Flue

Termination

Intake

Air

Termination

Boiler

Adapter

Flue

Termination

Intake Air

Termination

81 - 211

300715

FSBS3

FSRC3(R.C)

303889

KB80211 9353BUREZ-1*

9392

5300CI

9314TERM 2SVSLA03 2SVSTP03

2SVSRCX03 2SVSTEX0390

286

F303759

FSBS4

FSRC4(R.C.)

FSAIH04

303888

KB286600 9454BUREZ-1*

9492

5400CI

9414TERM 2SVSLA04 2SVSTP04

2SVSRCX04 2SVSTEX0490

* = This adapter must be used in addition to the boiler adapter for Saf-T vent pipe as shown in FIG. 3-11, unless approved vent
other than standard diameter is used. Consult a Heat Fab representative for questions.