Hydronic piping, 20°f temperature rise applications, 25°f temperature rise applications – Lochinvar KBII-I-O REV C 81 - 286 User Manual
Page 37: 35°f temperature rise applications
![background image](/manuals/168053/37/background.png)
37
Installation & Operation Manual
0
5
10
15
20
25
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
81
106
151
211
286
Flow Rate (GPM)
Pressure Drop vs. Flow (Includes Secondary Piping)
Pressure Drop (Feet of Head)
Figure 6-3 Pressure Drop vs. Flow
20°F Temperature Rise Applications
Model
GPM
FT/HD
Minimum Pipe
Size
Pump
Grundfos
TACO
B & G
Armstrong
81
7.5
24
1"
UPS26-99F
0011
NRF-36
E7
106
9.8
27
1"
UPS26-99F
0013
NRF-36
E11
151
14.0
20
1"
UPS26-99F
0011
NRF-36
E7
211
19.6
29
1"
UPS32-160
1400-50
PL-55
E9
286
26.5
15
1-1/4"
UPS32-80
1400-20
PL-36
E11
Table 6A Circulator Recommendations for Temperature Rise Applications_20°, 25°, and 35°
25°F Temperature Rise Applications
Model
GPM
FT/HD
Minimum Pipe
Size
Pump
Grundfos
TACO
B & G
Armstrong
81
5.9
15.0
1"
UPS15-58FC
0014
NRF-36
E7
106
7.7
17.5
1"
UPS26-99F
0014
NRF-36
E7
151
11.0
12.8
1"
UPS26-99F
0014
NRF-36
E7
211
15.5
19.0
1"
UPS26-99F
0013
NRF-36
E7
286
21.0
11.5
1-1/4"
UPS26-99F
0011
NRF-36
E7
Pumps listed in bold type are provided by the factory as the boiler circulation pump on standard altitude
models.
NOTICE
35°F Temperature Rise Applications
Model
GPM
FT/HD
Minimum Pipe
Size
Pump
Grundfos
TACO
B & G
Armstrong
81
4.2
7.3
1"
UPS15-58FC
007
NRF-22
Astro-30
106
5.5
9.3
1"
UPS15-58FC
007
NRF-22
Astro-30
151
7.9
9.5
1"
UPS15-58FC
008/0010
NRF-36
Astro-30
211
11.0
9.1
1"
UPS15-58FC
0010
NRF-36
Astro-50
286
15.0
7.3
1-1/4"
UP26-64F
008/0010
NRF-36
E7
Pumps listed in italicized type are provided by the factory as the boiler circulation pump on high altitude
models.
NOTICE
The temperature rise provided by a pump/model combination will decrease by 3% per 1000 feet of elevation.
NOTICE
6
Hydronic piping
(continued)