Vent/air termination – sidewall

4

Sidewall direct venting

ALTERNATE VENTING ARRANGEMENT

(IF SPACE PERMITS)

BIRD

SCREEN

12”

MIN

12” MIN

15” MAX

COUPLING

TO BOILER

INTAKE AIR

CONNECTION

FROM BOILER

VENT PIPE

CONNECTION

BIRD SCREEN

GRADE OR

SNOW LINE

Figure 4-1C Alternate PVC/CPVC Venting Arrangement
(if Space Allows) w/Field Supplied Fittings

VENT / AIR

TERMINATION

12"

MIN.

12"

MIN.

12"

MIN.

Figure 4-2A Clearance to Gravity Air Inlets

BIRD

SCREEN

(TYPICAL)

12”

MIN.

12”

MIN.

12”

MIN.

Figure 4-2B Alternate Clearance to Gravity Air Inlets
w/Field Supplied Fittings

5.

Maintain clearances as shown in FIG.’s 4-1A thru 4-3B,
pages 21 and 23. Also maintain the following:
a.

Vent must terminate:
• At least 6 feet from adjacent walls.
• No closer than 12 inches below roof overhang.
• At least 7 feet above any public walkway.
• At least 3 feet above any forced air intake within

10 feet.

• No closer than 12 inches below or horizontally

from any door or window or any other gravity air
inlet.

b.

Air inlet must terminate at least 12 inches above
grade or snow line; at least 12 inches below the vent
termination; and the vent pipe must not extend
more than 24 inches vertically outside the building
as shown in FIG. 4-1B.

c.

Do not terminate closer than 4 feet horizontally
from any electric meter, gas meter, regulator, relief
valve, or other equipment. Never terminate above or
below any of these within 4 feet horizontally.

6.

Locate terminations so they are not likely to be damaged by
foreign objects, such as stones or balls, or subject to buildup
of leaves or sediment.

TO BOILER
INTAKE AIR
CONNECTION

FROM BOILER
VENT PIPE
CONNECTION

BIRD SCREEN

12" MIN

12" MIN

15" MAX

MODELS 80 - 285

GRADE OR
SNOW LINE

Figure 4-1D Alternate PVC/CPVC/SS Venting
Arrangement - Typical Stainless Steel Sidewall
Termination of Air and Vent w/Field Supplied Fittings,
Utilizing 90° Elbow Intake

12" (305 MM) MIN

15" (381 MM) MAX

12" (305 MM) MIN

FROM BOILER

VENT PIPE

CONNECTION

TO BOILER

INTAKE AIR

CONNECTION

BIRD SCREEN

MODEL 285 WITH FASNSEAL ONLY

GRADE OR
SNOW LINE

Figure 4-1E Alternate SS Venting Arrangement -
Typical Stainless Steel Sidewall Termination of Air and
Vent w/Field Supplied Fittings, Utilizing FasNSeal’s
Hood Intake