Troubleshooting, Checking temperature sensors – Lochinvar Sync Condensing Boiler 1.3 User Manual

Page 45

background image

3

Troubleshooting

(continued)

45

Table 3B - Inlet/Outlet System Sensor Resistance vs. Temperature

Temperature

Resistance

Temperature

Resistance

50

18,780

158

1,990

68

12,263

176

1,458

86

8,194

194

1,084

104

5,592

212

817

122

3,893

--

--

140

2,760

--

--

Table 3C - Flue Temperature Sensor Resistance vs. Temperature

Temperature

Resistance

Temperature

Resistance

68

14,773

176

1,707

86

9,804

194

1,266

104

6,652

212

952

122

4,607

230

726

140

3,252

248

560

158

2,337

--

--

Table 3D - Outdoor Air Sensor Resistance vs. Temperature

Temperature

Resistance

Temperature

Resistance

-50

490,813

20

46,218

-40

336,606

30

34,558

-30

234,196

40

26,099

-20

165,180

50

19,900

10

118,018

60

15,311

0

85,362

70

11,883

10

62,465

80

9,299

Checking temperature sensors

The boiler temperature sensors (inlet water, outlet water, system water, flue, and outdoor air) are all resistance type devices. The
following tables show the correct values for the sensors at various temperatures. Use an ohmmeter to read the resistance of the
sensor at a known temperature. If the resistance of the sensor does not closely match its corresponding table, replace the sensor.