Service – Lochinvar Sync Condensing Boiler 1.3 User Manual

Page 18

background image

Setup Screen:

The Setup Screen allows access to seven (7) other screens for
adjusting control parameters.

These screens are as follows:

• Service / Setup - Allows access to change service
notification parameters, LCD backlight parameters, and
temperature

units.

• Night Setback - Allows access to change the date and time
and ON/OFF times for night setback.
• Setpoints - Allows access to change the system heat
set point, hot water generation set point, and ON/OFF
differentials.
• Cascade - Allows access to change the cascade parameters.
• Outdoor Reset - Allows access to change the reset curve
parameters.
• Pumps - Allows access to change pump delay timing.
• BMS - Allows access to change the 0 - 10Vdc BMS
parameters.

To change a parameter, press one of the seven screen buttons.
A list of parameters and their corresponding location are
located on pages 11 and 12, Table 1B. Once a Screen button
is pressed a list of adjustable parameters will appear.

Select the parameter to be adjusted by pressing the SELECT
button next to the parameter. The first time the parameters
are accessed, you will be required to enter the service
password. The service password is 5309. Using the keypad,
enter the password and then press the OK button. If the
password is not entered correctly, the screen will revert to the
Parameter List Screen and you will not be able to adjust the
parameters. If a digit has been entered incorrectly, press the
left arrow key on the keypad to back the digit up.

If the password has been entered correctly, the Parameter
Change Screen will appear. The Parameter Change Screen will
display the parameter being changed, the previous setting of the
parameter, and adjustment buttons.

To adjust the parameter, press the + or - buttons to change the
value being displayed. Once the parameter has been adjusted
to the desired setting, press the APPLY button to change the
parameter and return to the Parameter List Screen. If no further
changes are necessary, press the BACK button to return to the
Parameter List Screen. Once all the necessary adjustments
have been made, press the BACK button to return to the Setup
Screen. Repeat this procedure to adjust the parameters in other
screens.

Press the SAVE button to program all changes made to the
control parameters and return to the Status Screen. Leaving the
Setup Screen without pressing the SAVE button will erase the
changes made to the control parameters and revert them back
to their previous settings.

Time - The time is displayed in the upper right-hand corner of
the display. It is displayed in 24 hour format. Reference the
night setback parameters on page 24 for information regarding
adjusting the date and time.

Main button - Pressing this button brings up the Main Screen.
From this screen navigation to eight (8) other screens is
possible. Reference the Main Screen section on page 17 of this
manual for more information regarding this screen.

Save button - Pressing this button will save all changes made to
the control parameters.

Status button - Pressing this button displays the Status Screen.
This screen shows the current status of the SYNC boiler.

Reference pages 13 - 14 for more information regarding this
screen.

1

Service

CAUTION

Before changing parameters, note the settings so that the unit can be returned to its original operating
parameters.

18