beautypg.com

Command descriptions, Continued, Logout” command “netstat” command “port” command – Siemens DataNET Hub (DNH) User Manual

Page 88

background image

80

•••• Command Summary

2000585-001

Command Descriptions,

Continued

This command logs the user out of a session. The user must be logged
out of the local device to login to a remote device.

This command may be used to display statistics for the DataNET sec-
tion. If a link number is given, statistics are displayed for just that link. If
no link number is given, summary statistics for all DataNET links are
given. If the keyword “clear” is given, the statistics counters are reset to
zero

:

netstat dn [link] [clear]

Example:local> netstat dn clear

SCC 2: Subordinate

Link 9.

RUNNING

SCC 3: Principal (mux)Links 1 through 8.

RUNNING

SCC 4: Cross-link

Link 10.

RUNNING

DataNET Statistics for all DN Links

Frames Sent

4967

Frames Sent/Retried

60

Frames Sent/Redirected

60

Frames Sent w/Errors

0

Frames Sent UnACKnowledged

0

Frames Received

4372

Frames Receiver Not Ready

0

Frames Received w/Errors

0

Link down

54

local>

This command will enable or disable normal DataNET communication on
individual ports. Before placing a port into “test” mode (see test com-
mand below), the port must first be taken offline with:

port stop num

where num is a port number, 1 through 9.

This command may also be used to reset a port that has been automati-
cally taken out of service by the hub after detection of a DataNET topol-
ogy loop:

port start num

This will re-start normal DataNET communications on a port.

“logout” Command

“netstat” Command

“port” Command