Ethernet connections – Siemens DataNET Hub (DNH) User Manual

Page 54

background image

46

•••• Installation

2000585-001

Ethernet Connections,

Continued

1. The 10BASET data cable requires a minimum of two twisted pairs

(transmit pair and a receive pair). The type wire used should conform
to the AT&T D-inside wire (DWI & PDS), or IBM Type 3, or Category
3 or 5 data grade or equivalent specifications.

2. The maximum length of a 10BASET data cable can not exceed 328

feet (100 meters). Typically to increase the distance each DNH will
connect to a hub or other type of repeater/medium converter.

3. The cable should be terminated at both ends with RJ-45 STP male

connectors. The table below shows the RJ-45 wiring connections for
the DNH end of the cable.

Pin No.

MDI Function

1 TX+
2 TX-
3 RX+
4 NC
5 NC
6 RX-
7 NC
8 NC

10BASE-T Cable
Requirements