4 general electrical safety instructions, General electrical safety instructions – Sundance Spas CAMDEN 780 User Manual
Page 12
Page 8
780 SERIES
A Warning Sign is provided in your warranty packet. Please install at
a location near your spa, where it is visible to users of the spa. For
additional or replacement Warning Signs please contact your local
Sundance spas dealer and reference item number #6530-082.
3.3
Important Additional CSA Safety Instructions (Canada Only)
When using this electrical equipment, basic safety precautions should
always be followed, including the following:
1.
REAd ANd FOLLOW ALL INSTRUCTIONS.
2. A green colored terminal or a terminal marked G, Gr, Ground,
Grounding or the symbol* is located inside the supply terminal box
or compartment. To reduce the risk of electric shock, this terminal must
be connected to the grounding means provided in the electric supply
service panel with a continuous copper wire equivalent in size to the
circuit conductors that supply this equipment (*IEC Publication 417,
Symbol 5019).
3. At least two lugs marked “Bonding Lugs” are provided on the external
surface or on the inside of the supply terminal box/compartment. To
reduce the risk of electric shock, connect the local common bonding
grid in the area of the spa to these terminals with an insulated or bare
copper conductor not smaller than No. 6 AWG (10 mm²).
4. All field-installed metal components such as rails, ladders, drains
or other similar hardware within 10 feet (3m) of the spa shall be
bonded to the equipment grounding buss with copper conductors not
smaller than No. 6 AWG (10 mm²).
5.
SAvE THESE INSTRUCTIONS.
3.4
General Electrical Safety Instructions
Your new Sundance
®
780 Series Spa is equipped with a "state-of-
the-art" equipment system. It contains the most advanced safety and
self-protective equipment in the industry. Nonetheless, this spa must
be installed properly to ensure dependable usage. Please contact your
local Sundance dealer or local building department should you have any
questions regarding your installation.
Proper grounding is extremely important. Sundance spas are equipped
with a current collector system. A pressure wire connector is provided
on the surface of the control box, located outside the equipment door
(Figure B, page 16) to permit connection of a bonding wire between
this point and any ground metal equipment, metal water pipe or conduit
within 5 feet (1.5m) of the spa, or copper clad grounding rod buried
within 5 feet (1.5m) of the spa. Bonding wire must be at least No. 8 AWG
(8.4 mm²) solid copper wire. This is a most important safety assurance
feature.