beautypg.com

Displaying alarm status – Symmetricom EDGE CLOCK 1000 User Manual

Page 134

background image

Chapter 4 Provisioning the TimeProvider
Provisioning Alarms

134 TimeProvider User’s Guide

097-58001-02 Revision G – April 2008

Normal Response

TP-SSU 03-10-24 11:22:11

M

TS1000 COMPLD

"SYS,EQPT:MJ,PWRA,NSA,03-10-24 11-22-11:\"POWER A FAILED\""

"SYS,EQPT:MJ,EXPFAIL,SA,03-10-24 11-22-11:\"EXPANSION CONNECTIVITY FAILED\""

"IOC2,EQPT:MJ,CLKFREE,SA,03-10-24 11-25-15:\"CLOCK ENTERED FREE-RUN MODE\""

"INP1,T1:MN,INPLOS,NSA,03-10-24 11-25-16:\"LOS FAULT\""

"INP2,T1:MN,INPDISQ,NSA,03-10-24 11-25-17:\"INPUT DISQUALIFIED AS POSSIBLE

REFERENCE\""

"INP2,T1:MN,INPLOS,NSA,03-10-24 11-25-17:\"LOS FAULT\""

;

Displaying Alarm Status

The RTRV-COND command displays information about the current summary alarm
status of components within the TimeProvider. The active IOC reports alarms for the
Input, Output, and Expansion Panel.

RTRV-COND:[]::[];

This command always has an access level of USER.

Normal Response Format

^^^sid^date^time

M ^ctag^COMPLD

^^^”SYS:,,,,,

,,,

^^^”IMC:,

[^^^”IOC1:,,]

[^^^”IOC2:,,]

^^^”GPS:

^^^”PRS:

^^^”INP1:

^^^”INP2:

^^^”OUTA:

^^^”OUTB:

^^^”OUTC:

^^^”OUTD:

;

Description

ALL (or null)

Access Identifiers

This manual is related to the following products: