beautypg.com

Sentry Industries 5000 User Manual

Page 84

background image

SMC

sierra monitor corporation

Sentry Instruction Manual - Version 6

SERVICE

Page: 78

7.9 TOXIC GAS SENSOR MODULE

7.9.1 DESCRIPTION

Toxic Gas Sensor Modules include the following
models and default ranges:

5100-06

Chlorine -10 PPM

5100-07

Hydrogen - 2000 PPM

5100-12

Nitrogen Dioxide - 20 PPM

5100-13

Carbon Monoxide, High Range -
1,000 PPM

5100-10

Sulfur Dioxide - 100 PPM

5100-16

Carbon Monoxide, H2 Tolerant -
2,000 PPM

5100-19

Nitric Oxide - 20 PPM

5100-21

Hydrogen Chloride - 20 PPM

5100-22

Hydrogen Cyanide - 20 PPM

5100-27

Ethylene Oxide - 20 PPM

The Toxic Sensor Module includes a sensor
assembly and electronic assembly installed in an
explosion proof housing.

The sensor assembly includes a reuseable housing
and disposable electrochemical sensor. The
assembly screws into one hub of the sensor
module enclosure and plugs into the bottom
electronics card via a six pin connector.

Cabling from the controller connects to a three pin spring
loaded terminal strip on the electronics assembly.

7.9.2 TROUBLE ANALYSIS

Electrical adjustment, or replacement of the sensor will be
necessary under the following conditions:

Controller displays the following error messages

SENSOR FAILURE

LOW SENSITIVITY

False readings or alarms are received due to
sensor inaccuracy.

Warning: During sensor adjustments the concentration
reading on the controller will be inaccurate and alarm
level concentrations may be displayed. If false activation
of the alarm relays will cause a problem disconnect the
relay wiring prior to adjustment or turn the module off
using the "Change Module" mode.

NOTE

Although all the necessary data can be collected with a

voltmeter at the sensor module, some helpful

information can be displayed on the controller or

printed. See diagnostic codes 0004 and 0008 in

Appendix C.

7.9.3 ADJUSTMENT PROCEDURE

Prior to reading voltages and making adjustments perform
a visual inspection to confirm that there are no physical
problems such as water in the electronics enclosure,
wiring damage or corrosion.

Use Figure 7-11 to locate test points during the following
procedures.

7.9.3.1 SIGNAL ADJUSTMENT

It is unlikely that any electrical adjustment will be
required except when a new sensor is installed.

To make the electrical adjustment connect a voltmeter to

SIGNAL OUT

(pos) and

GND

(ground) and use

SPAN ADJ

potentiometer to adjust the voltage based on the
following:

1% of full scale = 0.02 VDC.

100% of full scale = 2.00 VDC.

7.9.3.2 SENSOR REPLACEMENT

The toxic gas sensor should be replaced when it can no
longer be calibrated correctly. Generally this is every
twenty four to thirty months.

Figure 7-11

Cover Plate - Toxic Gas Module