12. SERVICE PROCEDURES
7) Outdoor Fan Speed is not Switched from High to Low even when the Outdoor
Temperature Falls below 78
°
F. (C2462R Type)
6) Outdoor Fan does not Run.
• Check resistance of fan
motor winding.
• Check fan motor capacitor
OK
• Check continuity between
terminals on the compressor
motor magnetic contactor.
• Check fan rotation.
Rotate the fan gently once
or twice by hand.
0633_X_S
• Check fan casing
for foreign matter
on the inside.
Remove foreign
matter or repair.
Repair or replace.
Fan cannot
be rotated.
• Fan motor burnout
or foreign matter
in bearing.
8) Outdoor Fan Speed is not Switched from High to Med even when the Outdoor
Temperature Falls below 77
°
F.
Outdoor Fan Speed is not Switched from Med to Low even when the Outdoor
Temperature Falls below 59
°
F. (CL2462R Type)
1037_X_S
• Check the thermostat (23S).
• Check resistance of outdoor
temp sensor.
0722 _X_S
• Check outdoor unit P.C.B.
Ass’y
OK
- ECO-i WCHDZ20053 (2 pages)
- CL0951 (3 pages)
- ECO G SPW-GU075XH (9 pages)
- CM1972 (99 pages)
- CR365GX56 (1 page)
- 42XS32A (3 pages)
- CL2432A (3 pages)
- 9 (2 pages)
- KH3072R / C3072R (180 pages)
- CH0971 (2 pages)
- 26UW72R (2 pages)
- C2432 (17 pages)
- CR1304GDZH8 (1 page)
- KH2672R (48 pages)
- ECOi C0905DXHN8 (10 pages)
- CH1251 (98 pages)
- 30KS32A (3 pages)
- Concealed Duct & Heat Pump H 13.9-14.9 SEER (2 pages)
- 42TLS32A (3 pages)
- C1251 (83 pages)
- DHX3652 (114 pages)
- 42XHW72R (2 pages)
- 09KS71 (2 pages)
- C3632A (3 pages)
- 18KS72 (2 pages)
- 12XS71 (2 pages)
- ECO R410A (48 pages)
- KS2472 (117 pages)
- INVERTER SPLIT SYSTEM 8.53E+13 (24 pages)
- C3082 (104 pages)
- KHHS2672R (4 pages)
- CHX06052 (246 pages)
- CL1211 (16 pages)
- CH3082 (109 pages)
- Indoor Unit thx1852 (4 pages)
- 42TW72R (2 pages)
- KHS1872 (111 pages)
- C4232 (66 pages)
- CHDZ14053 (265 pages)
- CL0971 (4 pages)
- CHDX14053 (243 pages)
- 09KS51 (3 pages)
- 12RLS11 (3 pages)
- CL1852 (81 pages)