Service procedures – Sanyo CL2462R User Manual
Page 41

– 41 –
SM830092
12. SERVICE PROCEDURES
(b) Circuit breaker trips in several minutes after turning the air conditioner on.
• There is a possibility of short circuit.
2
Neither indoor unit nor outdoor unit runs.
A. Power is not supplied
0616_X_S
• Try to run both indoor and
outdoor units with another
remote control unit.
The other remote control
unit is defective.
OK
0615_X_S
• Check power supply.
Is power being supplied
to outdoor unit ?
Circuit breaker
is tripped.
Power failure.
Reset the breaker.
Wait for recovery
or consult power
supply company.
NO
B. Check remote control unit.
• Check capacity of circuit
breaker.
NO
• Check resistance of
outdoor fan motor winding.
2218_X_S
Is capacity of circuit
breaker sufficient ?
• Check resistance of
compressor motor winding.
Replace it with a
suitable one.
(= larger capacity)
• Check resistance of flap
motor winding.
- ECO-i WCHDZ20053 (2 pages)
- CL0951 (3 pages)
- ECO G SPW-GU075XH (9 pages)
- CM1972 (99 pages)
- CR365GX56 (1 page)
- 42XS32A (3 pages)
- CL2432A (3 pages)
- 9 (2 pages)
- KH3072R / C3072R (180 pages)
- CH0971 (2 pages)
- 26UW72R (2 pages)
- C2432 (17 pages)
- CR1304GDZH8 (1 page)
- KH2672R (48 pages)
- ECOi C0905DXHN8 (10 pages)
- CH1251 (98 pages)
- 30KS32A (3 pages)
- Concealed Duct & Heat Pump H 13.9-14.9 SEER (2 pages)
- 42TLS32A (3 pages)
- C1251 (83 pages)
- DHX3652 (114 pages)
- 42XHW72R (2 pages)
- 09KS71 (2 pages)
- C3632A (3 pages)
- 18KS72 (2 pages)
- 12XS71 (2 pages)
- ECO R410A (48 pages)
- KS2472 (117 pages)
- INVERTER SPLIT SYSTEM 8.53E+13 (24 pages)
- C3082 (104 pages)
- KHHS2672R (4 pages)
- CHX06052 (246 pages)
- CL1211 (16 pages)
- CH3082 (109 pages)
- Indoor Unit thx1852 (4 pages)
- 42TW72R (2 pages)
- KHS1872 (111 pages)
- C4232 (66 pages)
- CHDZ14053 (265 pages)
- CL0971 (4 pages)
- CHDX14053 (243 pages)
- 09KS51 (3 pages)
- 12RLS11 (3 pages)
- CL1852 (81 pages)