Square d model 100-700 plcs, Registers accessed, Square d tsx07 plcs – ICP DAS USA DB25 User Manual
Page 61: Ti505 series plcs, Passthrough port note
Application Notes – PLCs and Devices
55
S
QUARE
D
M
ODEL
100-700
PLC
S
Registers Accessed
The DN-3000 will only access registers in the Data Area of PLC memory (S0 to S9999). When entering
register numbers, only the offset into this area (0-9999) should be entered. For example, to access
register number S10, the value 10 should be entered. To access register number S999, the value 999
should be entered.
S
QUARE
D
TSX07
PLC
S
Registers Accessed
The DN-3000 will only access registers in the Memory Word Area of PLC memory (%MW0 to
%MW999). When entering register numbers, only the offset into this area (0-999) should be entered. For
example, to access register number %MW0, the value 0 should be entered. To access register number
%MW999, the value 999 should be entered.
TI505
S
ERIES
PLC
S
Registers Accessed
The DN-3000 will only access registers in the V Area of PLC memory (V1 to V9999). When entering
register numbers, only the offset into this area (1-9999) should be entered. For example, to access
register number V1, the value 1 should be entered. To access register number V9999, the value 9999
should be entered.
Passthrough Port Note
When using TISOFT PLC programming software on the passthrough port (Port 3) of the DN-3000, the
software must be invoked with the following parameters:
p1 T0 0 (for PC COM Port 1) OR
p2 T0 0 (for PC COM Port 2)
For example, if you are using a 545 PLC and you are using COM2 on your PC, you would invoke
TISOFT as follows:
TI545 p2 T0 0
These parameters will prevent the programming software from switching over to the Transparent Byte
Protocol, which is not supported by the DN-3000.