beautypg.com

Technical information, Dn-3000 – ICP DAS USA DB25 User Manual

Page 54

background image

Technical Information

48

C

ONFIGURATION

M

ODE

:

LED COLOR MEANING

Communication Port # 3

LED

Flashing Red-Green

Communicating with Computer

Status LED

Flashing Green

Configuration Mode


D

IAGNOSTIC

M

ODE

:

LED COLOR MEANING

Flashing Green

Port is Operational

Communication Port LEDs

Flashing Red or

Yellow

Port not Operational or Loopback

Connector not Installed

Status LED

Flashing Red

Diagnostics Mode

DN-3000

T

ROUBLESHOOTING

I

NFORMATION


The DN-3000 performs a self-test each time the unit is powered up or when the Mode Selection DIP
Switch is changed. When it detects a failure, it will report the type of failure on the Status LED. All
failures are reported as a flash code in which the DN-3000 will flash its Status LED yellow a designated
number of times followed by a pause. The flash code will repeat itself until the unit is powered off. The
possible errors that can be reported and the recommended actions are:


2 flashes followed by a pause
Random Access Memory Failure (RAM Failure)
Send the unit in for repair (Obtain RMA number first).

3 flashes followed by a pause
Firmware stored in ROM failed checksum test (ROM Failure)
Send the unit in for repair (Obtain RMA number first).

4 flashes followed by a pause
Unit Not Configured or EEPROM failure
If transferring your project file to the DN-3000 does not correct this error, send the unit in for
repair (Obtain RMA number first).

5 flashes followed by a pause
Invalid DIP Switch Setting
Verify that the DIP Switch is properly set to a valid operating mode (See DIP Switch Settings
in this section). If the DIP Switch is properly set, send the unit in for repair (Obtain RMA
number first).