Fp2132 sidewall vent graph, Khldv series gas fireplace, Fp1951 termination clearances venting installation – Monessen Hearth DIRECT VENT GAS FIREPLACE KHLDV400 User Manual

Page 14: How to use the vent graph

background image

14

73D0024

KHLDV Series Gas Fireplace

40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10

8
6
4
2

2  4  6  8 10 12 14 16 18 20

eg: A

FP2132
sidewall vent graph

V

G

G=6" (152mm)

F

F=6" (152mm)

V

V

G

G = Combustible 24"(610mm)

Noncombustible 18"(457mm)

Combustible &

Noncombustible

H = 24" (610mm)

J = 20" (508mm)

V

H

J

C = Maximum depth of 48" (1219mm)

for alcove location

D = Minimum width for back wall of

alcove location

Combustible - 38" (965mm)

Noncombustible - 24" (610mm)

E = Clearance from corner in alcove

location

Combustible - 6" (152mm)

Noncombustible - 2" (51mm)

E

V

D

C

C

Inside Corner

Alcove Location

Outside Corner

Balcony with No Side Wall

Balcony with Perpendicular

Side Wall

FP1951
termination clearances

VentInG InStaLLatIon

terMInatIon cLearanceS For BuILDInGS wItH coMBuStIBLe
anD noncoMBuStIBLe exterIorS

Figure 9 -
Allowable Venting Chart

How to uSe tHe Vent GrapH

The Vent Graph should be read in conjunction with the
following vent installation instructions to determine the
relationship between the vertical and horizontal dimensions
of the vent system.
1. Determine the height of the center of the horizontal vent

pipe exiting through the outer wall. Using this dimen-
sion on the Sidewall Vent Graph below, locate the point
intersecting with the slanted graph line.

2. From the point of this intersection, draw a vertical line

to the bottom of the graph.

3. Select the indicated dimension, and position the fire-

place in accordance with same.

Example: If the vertical dimension from the floor of the

fireplace is 11' (3.4 m) the horizontal run to the face of
the outer wall must not exceed 16' (4.9 m).

Sidewall Vent Graph showing the relationship between
vertical and horizontal dimensions for a Direct Vent flue
system.

Dimensions in

Feet

Combustible – 6" (152 mm)
Noncombustible – 2" (51mm)

Figure 10 -
Rear Wall Venting Graph

Horizontal dimension from the finished outside wall

to the center of the pipe on the fireplace

V

ertical Dimension From the Floor of Unit to the Center of the

Horizontal V

ent Pipe