KHLDV Series Gas Fireplace

InStaLLatIon precautIonS

Consult local building codes before beginning the
installation. The installer must make sure to select the
proper vent system for installation. Before installing vent
kit, the installer must read this fireplace manual and vent
kit instructions.
Only a qualified installer/service person should install vent-
ing system. The installer must follow these safety rules:

Wear gloves and safety glasses for protection.

Use extreme caution when using ladders or when

on rooftops.

Be aware of electrical wiring locations in walls and

ceilings.

The following actions will void the warranty on your vent-
ing system:

Installation of any damaged venting component.

Unauthorized modification of the venting system.

Installation of any component part not manufactured

or approved by MHSC.

Installation other than permitted by these instruc-

tions.

VentInG InStaLLatIon

w

arn

In

G

read all instructions completely and thoroughly before attempting
installation. Failure to do so could result in serious injury, property
damage or loss of life. operation of improperly installed and maintained
venting system could result in serious injury, property damage or loss
of life.

not

Ice

Failure to follow these instructions will void
the warranty.

w

arn

In

G

this fireplace must be vented to the outside. the venting system must
neVer be attached to a chimney serving a separate solid fuel burning
appliance. each gas appliance must use a separate vent system. Do not
use common vent systems.

**1”

FP2131
Vent pipe clearances

**1”

*3”

73”

(1854 mm)

w

arn

In

G

Horizontal sections of this vent system require a minimum of 3" clearances to combustibles at
the top of the flue and 1" clearance at the sides and bottom until the flue penetrates the outside
wall.
a minimum 1" clearance all around the flue is acceptable at this point of penetration. unless
the vertical run is 7Z\x" or higher from floor of fireplace, the clearance for horizontal run is 1" on
all sides.
Vertical sections of this vent system require a minimum of 2" clearance to combustibles at the
top of the unit directly above the stand-off. a minimum of 1" clearance all around the flue is
acceptable thereafter.

* A minimum of 3" clearance
to the top is required along
horizontal length until flue pipe
penetrates outside wall.
** A minimum 1" clearance
to combustibles permitted all
around flue at outside wall

24" Vertical Rise
Required Before
Horizontal Run

Figure 7 -
Combustible Clearances for Vent Pipe

FP2131