beautypg.com

Startup – Multiquip 20 KW Standby Generator MQP20P User Manual

Page 27

background image

MQp20p STaNDBY geNeRaTOR • OpeRaTiON aND paRTS MaNual — Rev. #1 (11/28/11) — page 27

StartuP

BeFORe STaRTiNg

1. Place the main circuit breaker (Figure 14) in the

OFF

position prior to starting the engine.

Figure 14. Main Circuit Breaker (OFF)

2. Connect the load to the receptacles on the Camlok

outlet box. See Figure 6.

3. Tighten terminal nuts securely to prevent load wires

from slipping out.

STaRTiNg (MaNual)

1. Press the

RuN button (Figure 15) on the controller to

start the engine.

Figure 15. Run Button

2. Once the engine starts, let the engine run for 1-2

minutes. At temperatures below freezing, this time

period must be extended to 2-4 minutes.

CauTiON

The engine’s exhaust contains harmful emissions.

alWaYS have adequate ventilation when operating.

Direct exhaust away from nearby personnel.

WaRNiNg

NeveR manually start the engine with the main circuit

breaker in the

ON position.

3. Listen for any abnormal noises. If any abnormalities

exist, shut down the engine and correct the problem.

4. Using the controller display, verify that the no-load

frequency and speed is approximately 62.5 Hz

(1875 rpm).

5. Place the main circuit breaker (Figure 16) to the

ON

position. Voltage is now available at the receptacles.

Figure 16. Main Circuit Breaker (ON)

STaRTiNg (auTO MODe)

DaNgeR

Before connecting the generator to a

building’s electrical system, a

licensed

electrician must install a transfer

switch. Serious damage to the building’s

electrical system may occur without a

transfer switch.

CauTiON

When connecting the generator to an automatic transfer

switch,

alWaYS have power applied to the generator’s

internal battery charger. This will ensure that the engine

will not fail due to a dead battery.

WaRNiNg

When running the generator in the

auTO mode, the

generator can start up at any time without warning.

NeveR attempt to perform any maintenance when the

generator is in the

auTO mode.

NOTICE

When the generator is placed in the

auTO mode, the

engine glow plugs will be warmed and the engine will

start automatically.

This manual is related to the following products: