Hbdv7 series direct vent gas fireplace, Venting information, General venting information - termination location – Monessen Hearth HBDV400N/PSC7 User Manual

Page 12

background image

HBDV7 Series Direct Vent Gas Fireplace

1

54D8000

VeNtING INFoRMAtIoN

X

VENT TERMINATION  

AIR SUPPLY INLET 

AREA WHERE TERMINAL IS NOT PERMITTED 

 

Fixed

Closed
Operable

Operable

Fixed

Closed

CFM145a 
DV Termin Location 
5/01/01 Rev. 12/05/01  
sta 

INSIDE 

CORNER DETAIL 

CFM145a 

GeNeRAl VeNtING INFoRMAtIoN - teRMINAtIoN loCAtIoN

A = Clearance above grade, veranda, porch,

1” (30 cm)

1” (30 cm)

deck, or balcony
B = Clearance to window or door that may be

6” (15 cm) for appliances

6” (15 cm) for appliances

opened

< 10,000BTU/h (3kW), 1” (30 cm)

< 10,000 BTU/h (3kW), 9”

for appliances > 10,000 Btuh (3kW) and

(3 cm) for appliances > 10,000

< 100,000 BTU/h (30kW), 36” (91 cm)

Btuh (3kW) and < 50,000 BTU/h

for appliances > 100,000 BTU/h (30kW)

(15kW), 1” (30 cm) for

appliances > 50,000 BTU/h(15kW)

C = Clearance to permanently closed window

1” (305 mm) recommended to

1” (305 mm) recommended to

prevent window condensation

prevent window condensation

D = Vertical clearance to ventilated soffit located

above the terminal within a horizontal

18” (458 mm)

18” (458 mm)

distance of ’ (610mm) from the center

line of the terminal
E = Clearance to unventilated soffit

1” (305 mm)

1” (305 mm)

F = Clearance to outside corner

see next page

see next page

G = Clearance to inside corner (see next page)

see next page

see next page

H = Clearance to each inside of center line

3’ (91 cm) within a height of 15’ (5 m)

3’ (91 cm) within a height of 15’

extended above meter/regulator assembly

above the meter/regulator assembly

(5 m) above the meter/regulator

assy

I = Clearance to service regulator vent outlet

3’ (91 cm)

3’ (91 cm)

J = Clearance to nonmechanical air supply inlet 6” (15 cm) for appliances < 10,000

6” (15 cm) for appliances

to building or the combustion air inlet to any BTU/h (3kW), 1” (30 cm) for

< 10,000 BTU/h (3kW), 9”

other appliances

appliances > 10,000 BTU/h (3kW) and

(3 cm) for appliances > 10,000

< 100,000 Btuh (30kW), 36” (91 cm)

BTU/h (3kW) and < 50,000 BTU/h

for appliances > 100,000 BTU/h (30kW)

(15kW), 1” (30 cm) for

appliances > 50,000 BTU/h(15kW)

K = Clearance to a mechanical air supply inlet

6’ (1.83 m)

3’ (91 cm) above if within 10'

(3 m) horizontally

L = Clearance above paved sidewalk or paved 7’ (.13 m)†

7’ (.13 m)†

driveway located on public property

M = Clearance under veranda, porch, deck or

1” (30 cm)*

1” (30cm)*

balcony

1 In accordance with the current CSA-B149 Installation Codes
In accordance with the current ANSI Z3.1/NFPA 54 National Fuel
Gas Codes
† A vent shall not terminate directly above a sidewalk or paved
driveway which is located between two single family

dwellings and serves both dwellings
* only permitted if veranda, porch, deck or balcony is fully open on a
minimum sides beneath the floor:

Canadian Installations

1

uS Installations

2

NOTE: 1. Local codes or regulations may require different

clearances.

. The special venting system used on Direct Vent Fireplaces

are certified as part of the appliance, with clearances

tested and approved by the listing agency.

3. MHSC assumes no responsibility for the improper

performance of the appliance when the venting system

does not meet these requirements.

Figure 11 -
Termination Locations