PU(H)-7,8, 10 (Upper blow)

(1) At a single installation

The obstacle is on the outlet side. (Fig 1)
The obstacle is in three directions. (Fig 2,3)
The obstacle is in four directions. (Fig 4)

The right and left side
and the back and forth
side must be opened.

However, the
outlet side must
be opened.

Fig 2

Service Panel

500 over

300 over

300

over

Fig 1

ceiling

1200

over

However, if the service
panel is an interior side,
the right or left side
need 500 over.

If this side is service
panel, you need 500
over. If this side is inlet,
you need 300 over.

300 over

300 over

Fig 4

All "A" is 500 over.
However, outlet side
must be opened.
And the obstacle in
two directions must be
lower than the unit.

A

A

AA

Fig 3

(2) Relation of unit when many set up unit. (Fig 5,6,7)

Fig 6

Fig 5

All "A" is 500 over.

500 over

500
over

300 over

300 over

500 over

300 over

A

A

A

A

300 over

Service-panel

If this side is
service panel,
you need 500 over.
If this side is inlet,
you need 300 over.

300 over

Fig 7 All "A" is 500 over in any case.

A

A

A

A

A

Service-panel