beautypg.com

Thermal drive unit – Motorola BT100 User Manual

Page 35

background image

3-10

Amplifier Setup

BT100 Installation and Operation Manual

ƒ

Low = channel 2 (55.25 MHz) or channel 3 (61.25 MHz)

ƒ

If the tilt is less than required, install a higher value input equalizer

ƒ

If the tilt is greater than required, install a lower value input equalizer

ƒ

If the high value equalizer provides too much tilt and the low value equalizer provides

too little tilt, use the lower value equalizer. Under-equalization is preferred to
over-equalization.

If you set up the BT100 using an SCS-*, you must increase or decrease the JXP input pad by
the amount of change you made in the SCS-* value. Therefore, to maintain a proper gain

level, it is necessary to adjust the input pad value as follows:

ƒ

For each increase in SCS-* value, decrease the input pad by 1 dB.

ƒ

For each decrease in SCS-* value, increase the input pad by 1 dB.

ƒ

If you replace an SFE with an SCS-*, reduce the value of the input pad by the value of

the SCS-*.

9

Measure the output level at the highest frequency.
It should be within 1 dB of the system design level. If it is not, you must adjust the midstage

pad (JXP) and/or the output pads (JXP OUT, JXP 1, JXP 3, JXP 4) accordingly. Refer to
Section 6, “Operating Tips,” for midstage/output padding information and recommendations.

Thermal Drive Unit

The TDU senses temperature and controls the Bode board. It is assumed that the cable is
subjected to the same or similar temperature; therefore, the TDU should not be used for

underground installations.
To set-up the TDU:

1

Place the jumper on the TDU (Figure 3-5) to the

LOW

,

MEDIUM

, or

HIGH

position to specify

the amount of cable for which the TDU compensates at the highest frequency preceding the

BT100 station.

Low = 0 dB to 15 dB of cable, medium = 15 dB to 37 dB of cable, and high = 38 dB or more of

cable.

Figure 3-5
TDU cable selector

2

Position the drive control select jumper (Figure 2-13) temporarily in the

MAN

position and

perform the complete procedure described in Manual Gain Control if not already completed.