beautypg.com

Gas-Fired Products PTS Series 100 User Manual

Page 45

background image

Form

#43343530

–44–

JJuly 08











Check external thermost

at

w

iring

and

thermost

at set point.

No

Ye

s

Remove red wire from the Low fire terminal,

is

there

24V

at the center C terminal?

No

Ye

s

Is

there

24V

at

the

HI

terminal on the gas valve?

No

Ye

s

With the thermost

at

set to low fire only does the low fire amber light come on af

ter 15 seconds?

No

Ye

s

Is

there

24V

between

the thermost

at

terminal

block

low

fire

cont

act and ground?

No

Ye

s

Check terminal connections, is the yellow wire connected

to

the

high

fire terminal?

Check external thermost

at

w

iring

and

thermost

at set point.

Switch terminal connections.

Red

wire

LO should be connected to ignition module W (TH) terminal.

Rep

air terminal

connections. Rest

art

troubleshooting.

No

Ye

s

Are the black wires to the amber light securely on the gas valve terminals?

Rep

air connection.

Rest

art

troubleshooting.

Replace amber light. Rest

art

troubleshooting.

No

Ye

s

Does the low fire amber light st

ay on

past 10 seconds?

No

Ye

s

Check the micro Amp

s at the FC-FC+

terminals of the module is it greater than

0.7µA

with

flame.

Turn on the gas valve?

Does LED on the ignition module flash three times?

Replace ignition module.

Check flame sense wire does it have continuity?

Cont

act factory for

assist

ance.

Replace flame sense wire.

Adjust terminal connection. Rest

art

troubleshooting.

No

Ye

s

Is

the

knob

on

the

gas

valve turned to the ON position?

No

Ye

s

Through the inspection window is there a flame visible during st

art up?

No

Ye

s

Is

the

heater

properly

grounded?

Correct grounding problem.

No

Ye

s

Check

the

terminal

on

the flame sense electrode, is it tight?

No

Ye

s

Remove and inspect flame sense electrode. Is it clean and the ceramic int

act?

Rep

air or replace

flame sense electrode.

See next p

age for

troubleshooting sequence.

No

Ye

s

Replace ignition module.

No

Ye

s

No

Ye

s

Is

there

24V

at

the

HI

terminal on the gas valve?

No

Ye

s

Does the high fire amber

light

come

on?

No

Ye

s

Is the there 24V between the thermost

at terminal

block

high

fire

cont

act

and ground (yellow wire)?

No

Ye

s

Check terminal connections to the gas valve, are they tight?

Check the red wires C should be connected

to

the

TISS

and LO connected to W (TH) module terminal.

Rep

air terminal

connections.

Rep

air terminal

connections. Rest

art

troubleshooting.

No

Ye

s

Are the black wires to the amber light securely on the gas valve terminals?

Rep

air connection.

Rest

art

troubleshooting.

Replace amber light. Rest

art

troubleshooting.

Troubleshooting continued

on

the

next

page.