COMMON VENTING OF MULTIPLE HEATERS IN CONFINED SPACES IS
PROHIBITED. If any heater connected to a common vent system for
multiple heaters is found inoperative, the heater should be
disconnected from the vent system and its entrance into the vent
system capped.

Multiple Heater Horizontal venting arrangement.

4” Diameter

single wall Vent

Flue Collar

adaptor

Plan View

Vent Cap

(Breidert or

equivalent Type L)

2” (5cm)

Clearance

Thimble

1/2” (12mm) fall per 20 ft

(6m) toward vent terminal

6” (15cm)

minimum

Swept Tee

4” Diameter

single wall Vent

Flue Collar

adaptor

2” (5cm)

Clearance

Thimble

1/2” (12mm) fall per 20 ft

(6m) toward vent terminal

6” (15cm)

minimum

Swept Y

See multiple

vent size table

for diameter

See multiple

vent size table

for diameter

VENT SIZING TABLE — Multiple Heater Venting

Number of Heaters

Horizontal and vertical

Vertical Only

1 2 3 4

PTS/U 40/25

4” 4” 4” 4”

PTS/U 50/30

4” 4” 4” 5”

PTS/U 75/50

4” 4” 5” 6”

PTS/U 100/65

4” 5” 6” 6”

PTS/U 125/80

4” 5” 6” 7”

PTS/U 150/100

4” 6” 7” 7”

PTS/U 175/110

4” 6” 7” 8”

PTS/U 200/125

4” 6” 7” 8”

COMMON VENT DIAMETER

(If a size is not available use the next larger size.)

B.

INDIRECT VENTING (UNVENTED HEATERS) — This heater requires ventilation in the building to dilute the
products of combustion and provide fresh air for efficient combustion. Where unvented heaters are used, gravity
or mechanical means shall be provided to supply and exhaust at least 4 CFM per 1,000 Btu/hr input of installed
heaters. Exhaust vents must be located at the highest point above and in the vicinity of the heaters, and the inlet
vents must be located below the level of the heaters. An exhaust hood (Part #42924000) must be placed on the
flue adapter collar located on the end of the last body section when used unvented and must be mounted only in
an downward position as shown.

Flue Adapter

Collar

#10 Self-Drill

Screws

(typical)

4” (10cm) Exhaust hood PN 42924000

(point down away from ceiling)