beautypg.com

10 t, Roduct, Pecifications – Goodman Mfg CPC CONVERCIAL SS-CPC90-150 User Manual

Page 6: Cont

background image

6

www.goodmanmfg.com

SS-CPC90-150

SS-CPC90-150

www.goodmanmfg.com

7

P

roduct

S

PecificationS

P

roduct

S

PecificationS

P

roduct

S

PecificationS

— 10 t

onS

(

cont

.)

CPC120

***4V***A*

CPC120

***7B***A*

CPC120

***7B***B*

CPC120

***7V***A*

Cooling Capacity
Total BTU/h

116,000

118,000

116,000

116,000

Sensible BTU/h

84,700

87,300

84,700

84,700

EER / IEER

11.3 / 13.0

11.5 / 11.5

11.3 / 11.5

11.3 / 13.0

Decibels

83

83

83

83

ARI Reference #s

5696558

5728006

5728007

5696558

Evaporator Motor / Coil
Motor Type

2-Speed Belt

Belt Drive

Belt Drive

2-Speed Belt

Indoor Nominal CFM

3,500

3,500

3,500

3,500

Indoor motor FLA (Cooling)

3.3

2.5

2.5

2.4

Horsepower - RPM

2.0/1725

2.0/1725

2.0/1725

2.0/1725

Piston Size (Cooling)

0.086

0.084

0.084

0.086

Filter Size (Qty)

(4) 16 x 24 x 2

(4) 16 x 24 x 2

(4) 16 x 24 x 2

(4) 16 x 24 x 2

Drain Size (NPT)

¾"

¾"

¾"

¾"

R-410A Refrigerant Charge Cir #1 & #2

125 oz.

220 oz.

125 oz.

125 oz.

Evaporator Coil Face Area (ft²)

10.2

10.2

10.2

10.2

Rows Deep / Fins per Inch

4 / 14

4 / 14

4 / 14

4 / 14

Belt Drive Evap Fan Data
# of Wheels (D x W)

(1) 15" x 15"

(1) 15" x 15"

(1) 15" x 15"

(1) 15" x 15"

Motor Sheave / Blower Sheave

VL40 / AK74

VL40 / AK74

VL40 / AK74

VL40 / AK74

Belt

AX50

AX51

AX51

AX50

Condenser Fan / Coil
Quantity of Condenser Fan Motors

2

2

2

2

Horsepower - RPM

⅓ - 1,075

⅓ - 1,125

⅓ - 1,125

⅓ - 1,125

Fan Diameter / # Fan Blades

22 / 3

22 / 3

22 / 3

22 / 3

Outdoor Nominal CFM

8,200

8,200

8,200

8,200

Face Area (ft²)

35.2

32.4

35.2

35.2

Rows Deep - Fins per Inch

'2 X2 / 27±1

2 / 2 - 22

'2 X2 / 27±1

'2 X2 / 27±1

Compressor
Quantity / Type / Stage

2 / Scroll / 1

2 / Scroll / 1

2 / Scroll / 1

2 / Scroll / 1

Compressor RLA / LRA ea.

7.8/52.0

5.7/38.9

5.7/38.9

5.7/38.9

Electrical Data
Voltage/Phase/ Frequency

460-3-60

575-3-60

575-3-60

575-3-60

Standard Max Static

1.4"

1.4"

1.4"

1.4"

Outdoor Fan RLA ea.

1.20

0.90

0.90

0.90

Total Unit Amps

21

16

16

16

Min. Circuit Ampacity¹

23

17

17

17

Max. Overcurrent Protection (amps)²

30

20

20

20

Entrance Power Supply

Locating

Dimple

Locating

Dimple

Locating

Dimple

Locating

Dimple

Entrance Control Voltage

Operating Weight (lbs)

1050

1135

1050

1050

Ship Weight (lbs)

1125

1175

1125

1125

¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

² May use fuses or HACR-type circuit breakers of the same size as noted.

Notes

• Always check the S&R plate for electrical data on the unit being installed.

• When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for

208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.