10 t, Roduct, Pecifications – Goodman Mfg CPC CONVERCIAL SS-CPC90-150 User Manual
Page 6: Cont
![background image](/manuals/112538/6/background.png)
6
www.goodmanmfg.com
SS-CPC90-150
SS-CPC90-150
www.goodmanmfg.com
7
P
roduct
S
PecificationS
P
roduct
S
PecificationS
P
roduct
S
PecificationS
— 10 t
onS
(
cont
.)
CPC120
***4V***A*
CPC120
***7B***A*
CPC120
***7B***B*
CPC120
***7V***A*
Cooling Capacity
Total BTU/h
116,000
118,000
116,000
116,000
Sensible BTU/h
84,700
87,300
84,700
84,700
EER / IEER
11.3 / 13.0
11.5 / 11.5
11.3 / 11.5
11.3 / 13.0
Decibels
83
83
83
83
ARI Reference #s
5696558
5728006
5728007
5696558
Evaporator Motor / Coil
Motor Type
2-Speed Belt
Belt Drive
Belt Drive
2-Speed Belt
Indoor Nominal CFM
3,500
3,500
3,500
3,500
Indoor motor FLA (Cooling)
3.3
2.5
2.5
2.4
Horsepower - RPM
2.0/1725
2.0/1725
2.0/1725
2.0/1725
Piston Size (Cooling)
0.086
0.084
0.084
0.086
Filter Size (Qty)
(4) 16 x 24 x 2
(4) 16 x 24 x 2
(4) 16 x 24 x 2
(4) 16 x 24 x 2
Drain Size (NPT)
¾"
¾"
¾"
¾"
R-410A Refrigerant Charge Cir #1 & #2
125 oz.
220 oz.
125 oz.
125 oz.
Evaporator Coil Face Area (ft²)
10.2
10.2
10.2
10.2
Rows Deep / Fins per Inch
4 / 14
4 / 14
4 / 14
4 / 14
Belt Drive Evap Fan Data
# of Wheels (D x W)
(1) 15" x 15"
(1) 15" x 15"
(1) 15" x 15"
(1) 15" x 15"
Motor Sheave / Blower Sheave
VL40 / AK74
VL40 / AK74
VL40 / AK74
VL40 / AK74
Belt
AX50
AX51
AX51
AX50
Condenser Fan / Coil
Quantity of Condenser Fan Motors
2
2
2
2
Horsepower - RPM
⅓ - 1,075
⅓ - 1,125
⅓ - 1,125
⅓ - 1,125
Fan Diameter / # Fan Blades
22 / 3
22 / 3
22 / 3
22 / 3
Outdoor Nominal CFM
8,200
8,200
8,200
8,200
Face Area (ft²)
35.2
32.4
35.2
35.2
Rows Deep - Fins per Inch
'2 X2 / 27±1
2 / 2 - 22
'2 X2 / 27±1
'2 X2 / 27±1
Compressor
Quantity / Type / Stage
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
Compressor RLA / LRA ea.
7.8/52.0
5.7/38.9
5.7/38.9
5.7/38.9
Electrical Data
Voltage/Phase/ Frequency
460-3-60
575-3-60
575-3-60
575-3-60
Standard Max Static
1.4"
1.4"
1.4"
1.4"
Outdoor Fan RLA ea.
1.20
0.90
0.90
0.90
Total Unit Amps
21
16
16
16
Min. Circuit Ampacity¹
23
17
17
17
Max. Overcurrent Protection (amps)²
30
20
20
20
Entrance Power Supply
Locating
Dimple
Locating
Dimple
Locating
Dimple
Locating
Dimple
Entrance Control Voltage
Operating Weight (lbs)
1050
1135
1050
1050
Ship Weight (lbs)
1125
1175
1125
1125
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Notes
• Always check the S&R plate for electrical data on the unit being installed.
• When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for
208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.