h

eat

k

it

e

leCtriCal

d

ata

(B

lower

o

nly

, h

eat

m

ode

) — 10 t

ons

m

inimUm

a

irflow

for

e

leCtriC

h

eat

Heater Size (kW)

Min. CFM

Down-shot

Min. CFM

Horizontal

15

4,000

4,000

30

4,000

4,000

43

4,000

4,000

Model and

Heat Kit Usage

MCA¹

at 208 / 240V

MOP² (amps)

at 208 / 240V

Actual kW

at 240V

Recommended

Airflow Range

CPC120***3B/V***

49

60

EHK3-16

48 / 55

50 / 60

15

3500 - 4500 CFM

EHK3-30

87 / 100

90 / 100

30

3500 - 4500 CFM

EHK3-45

121 / 139

125 / 150

43

4000 - 4500 CFM

Model and

Heat Kit Usage

MCA¹

at 480V

MOP² (amps)

at 480V

Actual kW

at 480V

Recommended

Airflow Range

CPC120***4B/V***

24

30

EHK4-16

27

30

15

3500 - 4500 CFM

EHK4-30

50

50

30

3500 - 4500 CFM

EHK4-45

70

70

43

4000 - 4500 CFM

Model and

Heat Kit Usage

MCA¹

at 575V

MOP² (amps)

at 575V

Actual kW

at 575V

Recommended

Airflow Range

CPC120***7B/V***

17

20

EHK7-16

22

25

15

3500 - 4500 CFM

EHK7-30

41

45

30

3500 - 4500 CFM

EHK7-45

57

60

43

4000 - 4500 CFM

¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protection device

kw C

orreCtion

f

aCtors

kW Correction Factor (for 1- & 3-Phase Units)

Supply Voltage

240

230

220

210

208

Correction Factor

1

0.93

0.82

0.78

0.76

kW Correction Factor (for 480V Units)

Supply Voltage

460

440

430

Correction Factor

0.92

0.84

0.8

For other voltage, use voltage² / 480²

kW Correction Factor (for 575V Units)

Supply Voltage

560

550

540

Correction Factor

0.95

0.91

0.88

Multiply rated kW by correction factor to get actual kW.