beautypg.com

12½ t, Kw c, Lectrical – Goodman Mfg CPC CONVERCIAL SS-CPC90-150 User Manual

Page 23: Lower

background image

22

www.goodmanmfg.com

SS-CPC90-150

SS-CPC90-150

www.goodmanmfg.com

23

P

roduct

S

PecificationS

P

roduct

S

PecificationS

h

eat

k

it

e

leCtriCal

d

ata

(B

lower

o

nly

, h

eat

m

ode

) — 12½ t

ons

Model and

Heat Kit Usage

MCA¹

at 208 / 240V

MOP² (amps)

at 208 / 240V

Actual kW

at 240V

Recommended

Airflow Range

CPC150***3B***

65

80

EHK3-16

65

80

15

4000 - 5600

EHK3-30

102

110

30

4300 - 5600

EHK3-45

141

150

43

4500 - 5600

Model and

Heat Kit Usage

MCA¹

at 480V

MOP² (amps)

at 480V

Actual kW

at 480V

Recommended

Airflow Range

CPC150***4B***

31

40

EHK4-16

31

40

15

4000 - 5600

EHK4-30

51

60

30

4300 - 5600

EHK4-45

71

80

43

4500 - 5600

Model and

Heat Kit Usage

MCA¹

at 575V

MOP² (amps)

at 575V

Actual kW

at 575V

Recommended

Airflow Range

CPC150***7B***

23

30

EHK7-16

24

30

15

4000 - 5600

EHK7-30

43

45

30

4300 - 5600

EHK7-45

59

60

43

4500 - 5600

¹ Minimum Circuit Ampacity (standard drive)
² Maximum Overcurrent Protection device (standard drive)

kw C

orreCtion

f

aCtors

kW Correction Factor (for 1- & 3-Phase Units)

Supply Voltage

240

230

220

210

208

Correction Factor

1

0.93

0.82

0.78

0.76

kW Correction Factor (for 480V Units)

Supply Voltage

460

440

430

Correction Factor

0.92

0.84

0.8

For other voltage, use voltage² / 480²

kW Correction Factor (for 575V Units)

Supply Voltage

560

550

540

Correction Factor

0.95

0.91

0.88

Multiply rated kW by correction factor to get actual kW.