Product specs — 10 tons, 10 t, Roduct – Goodman Mfg CPC CONVERCIAL SS-CPC90-150 User Manual
Page 5: Pecifications

4
www.goodmanmfg.com
SS-CPC90-150
SS-CPC90-150
www.goodmanmfg.com
5
P
roduct
S
PecificationS
P
roduct
S
PecificationS
P
roduct
S
PecificationS
— 10 t
onS
CPC120
***3B***A*
CPC120
***3B***B*
CPC120
***3V***A*
CPC120
***4B***A*
CPC120
***4B***B*
Cooling Capacity
Total BTU/h
118,000
116,000
116,000
118,000
116,000
Sensible BTU/h
87,300
84,700
84,700
87,300
84,700
EER / IEER
11.5 / 11.5
11.3 / 11.5
11.3 / 13.0
11.5 / 11.5
11.3 / 11.5
Decibels
83
83
83
83
83
ARI Reference #s
5728006
5728007
5696558
5728006
5728007
Evaporator Motor / Coil
Motor Type
Belt Drive
Belt Drive
2-Speed Belt
Belt Drive
Belt Drive
Indoor Nominal CFM
3,500
3,500
3,500
3,500
3,500
Indoor motor FLA (Cooling)
7.8
7.8
6.4
3.9
3.9
Horsepower - RPM
2.0/1725
2.0/1725
2.0/1725
2.0/1725
2.0/1725
Piston Size (Cooling)
0.086
0.086
0.086
0.086
0.086
Filter Size (Qty)
(4) 16 x 24 x 2
(4) 16 x 24 x 2
(4) 16 x 24 x 2
(4) 16 x 24 x 2
(4) 16 x 24 x 2
Drain Size (NPT)
¾"
¾"
¾"
¾"
¾"
R-410A Refrigerant Charge Cir #1 & #2
220 oz.
125 oz.
125 oz.
220 oz.
125 oz.
Evaporator Coil Face Area (ft²)
10.2
10.2
10.2
10.2
10.2
Rows Deep / Fins per Inch
4 / 14
4 / 14
4 / 14
4 / 14
4 / 14
Belt Drive Evap Fan Data
# of Wheels (D x W)
(1) 15" x 15"
(1) 15" x 15"
(1) 15" x 15"
(1) 15" x 15"
(1) 15" x 15"
Motor Sheave / Blower Sheave
VL40 / AK74
VL40 / AK74
VL40 / AK74
VL40 / AK74
VL40 / AK74
Belt
AX51
AX51
AX50
AX51
AX51
Condenser Fan / Coil
Quantity of Condenser Fan Motors
2
2
2
2
2
Horsepower - RPM
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
Fan Diameter / # Fan Blades
22 / 3
22 / 3
22 / 3
22 / 3
22 / 3
Outdoor Nominal CFM
8,200
8,200
8,200
8,200
8,200
Face Area (ft²)
32.4
35.2
35.2
32.4
35.2
Rows Deep - Fins per Inch
2 / 2 - 22
2 X2 / 27±1
2 X2 / 27±1
2 / 2 - 22
'2 X2 / 27±1
Compressor
Quantity / Type / Stage
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
Compressor RLA / LRA ea.
16/110.0
16/110.0
16/110.0
7.8/52.0
7.8/52.0
Electrical Data
Voltage/Phase/ Frequency
208/230-3-60
208/230-3-60
208/230-3-60
460-3-60
460-3-60
Standard Max Static
1.4"
1.4"
1.4"
1.4"
1.4"
Outdoor Fan RLA ea.
2.40
2.40
2.40
1.20
1.20
Total Unit Amps
45
45
43
22
22
Min. Circuit Ampacity¹
49
49
47
24
24
Max. Overcurrent Protection (amps)²
60
60
60
30
30
Entrance Power Supply
Locating
Dimple
Locating
Dimple
Locating
Dimple
Locating
Dimple
Locating
Dimple
Entrance Control Voltage
Operating Weight (lbs)
1135
1050
1050
1135
1050
Ship Weight (lbs)
1175
1125
1125
1175
1125
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Notes
• Always check the S&R plate for electrical data on the unit being installed.
• When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for
208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.