Product specs — 7½ tons, 7½ t, Roduct – Goodman Mfg CPC CONVERCIAL SS-CPC90-150 User Manual
Page 3: Pecifications
![background image](/manuals/112538/3/background.png)
2
www.goodmanmfg.com
SS-CPC90-150
SS-CPC90-150
www.goodmanmfg.com
3
P
roduct
S
PecificationS
P
roduct
S
PecificationS
P
roduct
S
PecificationS
— 7½ t
onS
CPC090
***3B***B*
CPC090
***3B***C*
CPC090
***4B***B*
CPC090
***4B***C*
CPC090
***7B***B*
CPC090
***7B***C*
Cooling Capacity
Total BTU/h
90,000
88,000
90,000
88,000
90,000
88,000
Sensible BTU/h
64,000
65,100
64,000
65,100
64,000
65,100
EER / IEER
11.5 / 11.5
11.3 / 11.5
11.5 / 11.5
11.3 / 11.5
11.5 / 11.5
11.3 / 11.5
Decibels
82
82
82
82
82
82
AHRI Reference #s
5104770
5589862
5104770
5589862
5104770
5589862
Evaporator Motor / Coil
Motor Type
Belt Drive
Belt Drive
Belt Drive
Belt Drive
Belt Drive
Belt Drive
Indoor Nominal CFM
3,000
3,000
3,000
3,000
3,000
3,000
Indoor Motor FLA (Cooling)
5.0
5.0
2.5
2.5
2.3
2.3
Horsepower / RPM
1.5 / 1745
1.5 / 1745
1.5 / 1745
1.5 / 1745
1.5 / 1725
1.5 / 1725
Piston Size (Cooling)
0.078
0.078
0.078
0.078
0.078
0.078
Filter Size (Qty)
16 x 20 x 2
16 x 20 x 2
16 x 20 x 2
16 x 20 x 2
16 x 20 x 2
16 x 20 x 2
Drain Size (NPT)
¾"
¾"
¾"
¾"
¾"
¾"
R-410A Refrigerant Charge Cir #1 & #2
175
100 oz.
175
100 oz.
175
100 oz.
Evaporator Coil Face Area (ft²)
8.9
8.9
8.9
8.9
8.9
8.9
Rows Deep / Fins per Inch
4 / 16
4 / 16
4 / 16
4 / 16
4 / 16
4 / 16
Belt Drive Evap Fan Data
# of Wheels (D x W)
1 (15" x 12")
1 (15" x 12")
1 (15" x 12")
1 (15" x 12")
1 (15" x 12")
1 (15" x 12")
Motor Sheave / Blower Sheave
VL40 / AK74
VL40 / AK74
VL40 / AK74
VL40 / AK74
VL40 / AK74
VL40 / AK74
Belt
AX51
AX51
AX51
AX51
AX51
AX51
Condenser Fan / Coil
Quantity of Condenser Fan Motors
2
2
2
2
2
2
Horsepower - RPM
¼ - 1075
¼ - 1075
¼ - 890
¼ - 890
¼ - 1,075
¼ - 1,075
Fan Diameter / # Fan Blades
22 / 4
22 / 4
22 / 4
22 / 4
22 / 4
22 / 4
Outdoor Nominal CFM
7,200
7,200
7,200
7,200
7,200
7,200
Face Area (ft²)
36
28.8
36
28.8
36
28.8
Rows Deep / Fins per Inch
2 / 22
2 X2 / 27±1
2 / 22
'2 X2 / 27±1
2 / 22
'2 X2 / 27±1
Compressor
Quantity / Type / Stage
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
2 / Scroll / 1
Compressor RLA / LRA
13.1 / 83.1
13.1 / 83.1
6.1 / 41.0
6.1 / 41.0
4.4 / 33.0
4.4 / 33.0
Electrical Data
Voltage-Phase-Frequency
208/230-3-60
208/230-3-60
460-3-60
460-3-60
575-3-60
575-3-60
Max External Static
1.0"
1.0"
1.0"
1.0"
1.0"
1.0"
Outdoor Fan HP / RLA
(2) ¼ / 1.4
(2) ¼ / 1.4
(2) ¼ / 0.8
(2) ¼ / 0.8
(2) ¼ / 0.6
(2) ¼ / 0.6
Total Unit Amps
34.0
34.0
16.3
16.3
12.3
12.3
Min. Circuit Ampacity¹
37.3
37.3
17.8
17.8
13.4
13.4
Max. Overcurrent Protection (amps)²
50
50
20
20
15
15
Entrance Power Supply
Locating
Dimple
Locating
Dimple
Locating
Dimple
Locating
Dimple
Locating
Dimple
Locating
Dimple
Entrance Control Voltage
Operating Weight (lbs)
975
1010
975
1010
975
1010
Ship Weight (lbs)
1000
1085
1000
1085
1000
1085
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Notes
• Always check the S&R plate for electrical data on the unit being installed.
• When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for
208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.