P
roduct
S
PecificationS
P
roduct
S
PecificationS
h
eat
k
it
e
leCtriCal
d
ata
(B
lower
o
nly
, h
eat
m
ode
) — 8½ t
ons
Model and
Heat Kit Usage
MCA¹
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
(Downshot)
Recommended
Airflow Range
(Horizontal)
CPC102***3B***
43
50
---
---
---
EHK3-16
55
60
15
3400 - 3825 CFM
3400 - 3825 CFM
EHK3-30
100
100
30
3400 - 3825 CFM
3400 - 3825 CFM
EHK3-45
139
150
43
3400 - 3825 CFM
3400 - 3825 CFM
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW
at 480V
Recommended
Airflow Range
(Downshot)
Recommended
Airflow Range
(Horizontal)
CPC102***4B***
20
25
---
---
---
EHK4-16
27
30
15
3400 - 3825 CFM
3400 - 3825 CFM
EHK4-30
50
50
30
3400 - 3825 CFM
3400 - 3825 CFM
EHK4-45
70
70
43
3400 - 3825 CFM
3400 - 3825 CFM
Model and
Heat Kit Usage
MCA¹
at 575V
MOP² (amps)
at 575V
Actual kW
at 575V
Recommended
Airflow Range
(Downshot)
Recommended
Airflow Range
(Horizontal)
CPC102***7B***
17
20
---
---
---
EHK7-16
22
25
15
3400 - 3825 CFM
3400 - 3825 CFM
EHK7-30
41
45
30
3400 - 3825 CFM
3400 - 3825 CFM
EHK7-45
57
60
43
3400 - 3825 CFM
3400 - 3825 CFM
¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protection device
^ - EHK Heater Kits above require a three-phase power supply
kw C
orreCtion
f
aCtors
kW Correction Factor (for 1- & 3-Phase Units)
Supply Voltage
240
230
220
210
208
Correction Factor
1
0.93
0.82
0.78
0.76
kW Correction Factor (for 480V Units)
Supply Voltage
460
440
430
Correction Factor
0.92
0.84
0.8
For other voltage, use voltage² / 480²
kW Correction Factor (for 575V Units)
Supply Voltage
560
550
540
Correction Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW.