beautypg.com

8½ t, Kw c, Lectrical – Goodman Mfg CPC CONVERCIAL SS-CPC90-150 User Manual

Page 21: Lower

background image

20

www.goodmanmfg.com

SS-CPC90-150

SS-CPC90-150

www.goodmanmfg.com

21

P

roduct

S

PecificationS

P

roduct

S

PecificationS

h

eat

k

it

e

leCtriCal

d

ata

(B

lower

o

nly

, h

eat

m

ode

) — 8½ t

ons

Model and

Heat Kit Usage

MCA¹

at 208 / 240V

MOP² (amps)

at 208 / 240V

Actual kW

at 240V

Recommended

Airflow Range

(Downshot)

Recommended

Airflow Range

(Horizontal)

CPC102***3B***

43

50

---

---

---

EHK3-16

55

60

15

3400 - 3825 CFM

3400 - 3825 CFM

EHK3-30

100

100

30

3400 - 3825 CFM

3400 - 3825 CFM

EHK3-45

139

150

43

3400 - 3825 CFM

3400 - 3825 CFM

Model and

Heat Kit Usage

MCA¹

at 480V

MOP² (amps)

at 480V

Actual kW

at 480V

Recommended

Airflow Range

(Downshot)

Recommended

Airflow Range

(Horizontal)

CPC102***4B***

20

25

---

---

---

EHK4-16

27

30

15

3400 - 3825 CFM

3400 - 3825 CFM

EHK4-30

50

50

30

3400 - 3825 CFM

3400 - 3825 CFM

EHK4-45

70

70

43

3400 - 3825 CFM

3400 - 3825 CFM

Model and

Heat Kit Usage

MCA¹

at 575V

MOP² (amps)

at 575V

Actual kW

at 575V

Recommended

Airflow Range

(Downshot)

Recommended

Airflow Range

(Horizontal)

CPC102***7B***

17

20

---

---

---

EHK7-16

22

25

15

3400 - 3825 CFM

3400 - 3825 CFM

EHK7-30

41

45

30

3400 - 3825 CFM

3400 - 3825 CFM

EHK7-45

57

60

43

3400 - 3825 CFM

3400 - 3825 CFM

¹ Minimum Circuit Ampacity
² Maximum Overcurrent Protection device
^ - EHK Heater Kits above require a three-phase power supply

kw C

orreCtion

f

aCtors

kW Correction Factor (for 1- & 3-Phase Units)

Supply Voltage

240

230

220

210

208

Correction Factor

1

0.93

0.82

0.78

0.76

kW Correction Factor (for 480V Units)

Supply Voltage

460

440

430

Correction Factor

0.92

0.84

0.8

For other voltage, use voltage² / 480²

kW Correction Factor (for 575V Units)

Supply Voltage

560

550

540

Correction Factor

0.95

0.91

0.88

Multiply rated kW by correction factor to get actual kW.