XII. Thermistor fault indication


The electronic controller flashes the filter LED when a thermistor fault is detected. The filter
LED blinking according to the time specified until the thermistor fault is rectified.

1. Heat Overload Protection Algorithm

Large-Split Heatpump
























Large Split Heat Mode Protection Control Sequence *


Legend:
Comp. -

Compressor

OD

-

Outdoor


* Indoor fan runs according to section IV cool fan prevention in heat mode.

Comp. ON
OD Fan ON
ID Fan Set

Comp. ON
OD Fan ON
ID Fan Set

Comp. ON
OD Fan OFF
ID Fan High

Comp. OFF
OD Fan OFF
ID Fan High

Comp. ON
OD Fan ON
ID Fan Set

Comp. ON
OD Fan ON
ID Fan Set

Comp. ON
OD Fan OFF
ID Fan High

Comp. ON
OD Fan OFF
ID Fan High

Comp. OFF
OD Fan OFF
ID Fan High

Indoor coil
thermistor

46

°

C

50

°

C

65

°

C