Outdoor Coil De-icing in Heat Mode (applicable on Heat Pump Unit only)


The air-con controller heats up the outdoor coil to melt the ice formed at outdoor coil. To
achieve this, the compressor must be turned on, while the 4-way valve must be turned off.
During this period, the indoor fan must be switched off with exception condition as stated in
Note 1. otherwise it will fill the room with cool air and cause discomfort to the users.


























Defrost Time Chart




Defrost thermistor below 40

°

C

Below –4

°

C

Compressor ON

OFF

4-way valve ON

OFF

Outdoor fan ON

OFF


Defrost counter

Indoor fan ON

OFF

*Low

Max 8 min

60 sec.

30 sec.

60 sec.

60 sec.

Hot start