Fedders R407C User Manual
Page 53
F6
3.
3-min. compressor switch on delay
The compressor is not switched on again immediately after being switched off. The
air-con controller waits for 3 minutes before turning it on again to protect it.
This protective measure applies throughout the operation of the air-con except on
power-up.
4.
60-second 4-way valve delay (applicable on Heat Pump Unit only)
This refers to the 60-second delay after turning off
compressor before the 4-way valve is switched over from off to on or vice-versa.
This delay allows the safe, gradual transition of the air-con operation from a cooling
function to heating function or vice versa.
5.
Cool fan prevention in heat mode (applicable on Heat Pump Unit only)
When compressor starts in heating operation or after defrosting, the indoor fan
changes the speed due to the indoor coil thermistor temperature and operation time to
blow out warm air.The indoor fan runs according to the following table during heat
mode:
STEP 1:
ID Coil Temp., T T<=28
°
C
28
°
C ° C T>=30 ° C ID Fan STOP * LOW STEP 2: ID Coil Temp., T T<=33 ° C 33 ° C ° C T>=36 ° C ID Fan LOW * SET ID Coil Temp., T T<=46 ° C 46 ° C ° C T>=50 ° C ID Fan SET * HIGH The start-up warm airflow control program is regardless room temperature. The Indoor coil icing prevention in cool mode Outdoor coil icing prevention in heat mode (applicable on Heat Pump Unit only)
STEP 3:
* Maintain current state
indoor fan is also not switched on while the outdoor coil is being de-iced for the same
reason.
6.
Should the indoor coil temperature dip to 2°C or lower in cool mode for at least 2
mins, de-icing will be executed to remove the ice formed at the indoor coil. De-icing
will be stopped when the indoor coil temperature rises to 10°C or higher or 10 mins
lapse.
7.
If the outdoor coil temperature dips to below -4°C in heat mode. It will perform De-
ice according to a specified algorithm, and de-ice the outdoor coil if necessary.