PREPARATION OF PIPING

Pipe Length, Elevation and refrigerant charge

Cutting The Pipe And The Cables.

• Measure the distance between the

indoor and the outdoor units.

• Cut the pipe length about 10% more

than the measured distance.

• Cut the electrical cable with about 2

metres more than the measured dis-

tance.

• Each outdoor unit comes with a

refrigerant charge that is sufficient for
use with interconnecting tubing up to
7.5 metres.

• If the required interconnecting tube

exceeds 5 metres, for each additional
metre, add the amount of refrigerant
according to the table as shown below.

Max. Piping
Length per
Indoor Unit

Max. Elevation

per Indoor Unit

• The recommended maximum allowable

tubing length between indoor and

outdoor is 15 metres.

• The recommended maximum allowable

elevation between indoor and outdoor is

5 metres.

Liquid Pipe

Size

1/4”

Additional

Refrigerant

3/8”

21 g/m

57 g/m