C11

Connecting The Piping To The Indoor Unit

• Align the center of the piping

and then sufficiently tighten the

flare nut with fingers, tighten

the flare nut with torque wrench

according to the table as shown

below.

Flare nut

Indoor unit tubing

Torque
wrench

Spanner

Pipe Size

Diameter

Torque (N.m)

35.6 - 44.4

9.52mm (3/8”)

15.87mm (5/8”)

58.7 - 73.2

Torque Table

INDOOR UNIT INSTALLATION