Appendix b.3. driver error messages – FieldServer Omron FINS FS-8704-16 User Manual

Page 35

background image

FS-8704-16 Omron FINS Manual Page 35 of 38

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]

Appendix B.3. Driver Error Messages

Some configuration errors might produce an error every time a poll is generated. This will fill the error buffer
quickly and not add any clarity. For this reason the driver suppresses subsequent similar messages on the System
Error Screen. Thus it is possible for the same error produced by multiple Map Descriptors to produce only one
error message on the System Error screen. The driver displays subsequent error messages on the Driver Messages
screen.

Note : In the actual message you will see that %d has been replaced by an integer, %s by text indicating a data
array name or map descriptor name and %x by two hex characters.

Error Message

Description and Action Required

FINS_UDP#1: Err. Not Enough Space for
<%d> items.
When offset <%d> DA <%s> MD <%s>
MRC <%2X> SRC<%2X>

Data array length needs to be increased.10

FINS_UDP#2: Err. MD <%s>. Error Returned
by PLC.
MRC <%2X> SRC<%2X>
Main End Code <%2X> Sub End Code <%2X>
See Driver Manual for End Codes detail...

This message shows a request that produced this error at the PLC.
Check Appendix A.1 to see the detail for error and action.

FINS_UDP#3: FYI. MRC<%2X> SRC<%2X>
Not Supported

This command is not supported by the Driver.

FINS_UDP#4: ERR. Poll to %s Failed

Check Server having this IP,
Check cables and connections.

FINS_UDP#11:

Err.

Station

Reqd/Ext

<%d/%d>

Response from PLC is not addressed to this Client.

FINS_UDP#12: Err. Mrc-Src Reqd/Ext <%2X-
%2X/%2X-%2X>

Response from PLC not for current request.

FINS_UDP#21: Err. Message from PLC is Not
a Response>
MRC <%2X> SRC <%2x> MD <%s>

Message from PLC for shown request is not a response.

FINS_UDP#22: Err. Unknown Device with
Parameters...
Reqd/Ext dna <%d/%d> node <%d/%d> unit
<%d/%d>

Response from PLC ignored because mismatching for any shown
parameters.

FINS_UDP#23: Err. Message Sequence Not
Matched.Reqd/Ext <%d/%d>
MRC <%2X> SRC <%2X> MD <%s>

Response from PLC ignored because of mismatching request-
response sequence Id.

FINS_UDP#24: FYI. Bad Start<%2X>

The message was ignored because the first byte was bad.

FINS_UDP#31 : FYI Net_Number set to 1
Node <%s>

The Net_Number parameter is 0 or not specified. The Driver will
automatically change it to the default of 1

10

Some error messages require that the user correct a problem in the configuration. This is done by editing the

configuration CSV file, downloading the modified file and resetting the FieldServer to have the changes take effect.