Appendix A.2. PLC status to execute commands

PLC Type

Memory
Type

Command name

Run
Mode

Monitor
Mode

Program
Mode

Access right
5

UM Read
Protection
6

DIP UM Protection7

CS1/CJ1 Series

I/O Memory

MEMORY

AREA

READ

OK

OK

OK

OK

OK

OK

MEMORY

AREA

WRITE

OK

OK

OK

OK

OK

OK

Operating
Mode
Changes

RUN

OK

OK

OK

Disabled

OK

OK

STOP

OK

OK

OK

Disabled

OK

OK

Time

Data

Access

CLOCK READ

OK

OK

OK

OK

OK

OK

CLOCK WRITE

OK

OK

OK

Disabled

OK

OK

Status
Reading

CPU UNIT STATUS
READ

OK

OK

OK

OK

OK

OK

CYCLE TIME READ

OK

OK

Disabled

OK

OK

OK

5

Access Right at Other Device: The Access right at other device column tells whether the CPU Unit can or cannot receive a command when another device has

the access right to the CPU Unit.

6

UM Read Protection: The UM read protection column tells whether the CPU Unit can or cannot receive the command when UM (user memory) is protected

from a Peripheral Device.

7

DIP Switch UM Protection: The DIP switch UM protection column tells whether the CPU Unit can or cannot receive a command when UM is write-protected

by turning ON pin 1 of the DIP switch on the CPU Unit’s front panel.