beautypg.com

Driver specific map descriptor parameters – FieldServer Omron FINS FS-8704-16 User Manual

Page 19

background image

FS-8704-16 Omron FINS Manual Page 19 of 38

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]

5.3.2 Driver Specific Map Descriptor Parameters

Column Title

Function

Legal Values

Node_Name

Name of Node to fetch data from

One of the node names specified in
“Server Node Descriptor” above

*Data_Type
(see Note1 Appendix A.1)

Data type

CIO-WORD, WR-WORD, HR-WORD,
AR-WORD, EM-WORD

Length

Length of Map Descriptor

1 to maximum specified in Data
Array section above

*Address

Starting address of read block

0,100, 32767 etc
see section 6.1 for detail

*Memory_Code
(see Note1 Appendix A.1)

Memory code for PLC memory type

B0, B1, B2, B3, 82, 98 and
A0 ---- AC

*Command_Name
(see Note2 Appendix A.1)

Name of the command

MEMORY AREA READ
MEMORY AREA WRITE
RUN-STOP
CLOCK READ
CLOCK WRITE
CYCLE TIME READ
CPU UNIT STATUS READ

*MRC
(see Note2 Appendix A.1)

Main Request Code

1,4,6,7

*SRC
(see Note2 Appendix A.1)

Sub Request Code

1,2,20

*Unit_Number

Unit number of CPU at PLC

0,1,2 etc