Driver specific map descriptor parameters – FieldServer Omron FINS FS-8704-16 User Manual
Page 19
FS-8704-16 Omron FINS Manual Page 19 of 38
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: [email protected]
5.3.2 Driver Specific Map Descriptor Parameters
Column Title
Function
Legal Values
Node_Name
Name of Node to fetch data from
One of the node names specified in
“Server Node Descriptor” above
*Data_Type
(see Note1 Appendix A.1)
Data type
CIO-WORD, WR-WORD, HR-WORD,
AR-WORD, EM-WORD
Length
Length of Map Descriptor
1 to maximum specified in Data
Array section above
*Address
Starting address of read block
0,100, 32767 etc
see section 6.1 for detail
*Memory_Code
(see Note1 Appendix A.1)
Memory code for PLC memory type
B0, B1, B2, B3, 82, 98 and
A0 ---- AC
*Command_Name
(see Note2 Appendix A.1)
Name of the command
MEMORY AREA READ
MEMORY AREA WRITE
RUN-STOP
CLOCK READ
CLOCK WRITE
CYCLE TIME READ
CPU UNIT STATUS READ
*MRC
(see Note2 Appendix A.1)
Main Request Code
1,4,6,7
*SRC
(see Note2 Appendix A.1)
Sub Request Code
1,2,20
*Unit_Number
Unit number of CPU at PLC
0,1,2 etc