FS-8700-41 Simplex 4100 Driver Manual

Page 6 of 48

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: [email protected]

3

HARDWARE CONNECTIONS

The FieldServer is connected to the Simplex Device’s RS-232 port of device type "COMPUTER", the following port
attributes may be configured specifically for that particular port:

Ensure that these settings correspond to the settings described in section 4 of this document.

3.1

Sim4100 Panel

Setting

Default

Options

Baud Rate

9600

75, 110, 134.5, 300, 600, 1200, 1800, 2000, 2400, 4800, 9600, 19200

Parity

EVEN

1

ODD, EVEN, MARK, SPACE, NONE

Data Bits

8

7 or 8

Stop Bits

1

1 or 2

3.2

Sim4100U Panel

Setting

Default Options

Baud Rate 9600

75, 110, 134.5, 300, 600, 1200, 1800, 2000, 2400, 4800, 9600, 19200

Parity

NONE

1

ODD, EVEN, MARK, SPACE, NONE

Data Bits

8

7 or 8

Stop Bits

1

1 or 2

The following are the Simplex, recommended connections to be used in cabling between the 4100 and the
FieldServer device. For the computer device, the standard EIA signal description, and the 25 pin (DB25) and 9 pin
(DB9) connector assignments are shown.

4100 Host

Cable

Computer

4100

Signal

Signal DB25Pin DB9Pin

Port ATB1 Port BTB2 DB25 Pin
8

1

2

TXD

RXD

2

2

6

3

3

RXD

TXD

3

3

7

2

4

RTS

2

RTS

4

7

5

4

5

CTS

CTS

5

8

4

5

7

GND

──

GND

7

5

1

Odd or Even parity is recommended (by Simplex) to provide additional error detection at the character level.

2

The driver does not support the Simplex RTS/CTS handshaking model. Therefore deselect the HSHAKE terminal flag or connect CTS to RTS

with a jumper on the 4100 side